1. The data format of the power supply response to the host computer:
Device number
ID (1 byte) +
command code
(1 byte) +
operation code
(1 byte) +
data
(4 byte) +
check
code
(1 byte)
Device
ID
1-28
ID
number corresponding to each
inverter power supply
Command
code
ASCII
HEX
R '
0x52
Read response
W
0x57
Write response
Opcode
There is a detailed description later
Operation object
data
The low byte is in the front, the high bytes are in the
back, there is a detailed description later
4-
byte data returned
Check code
Sum of the first
7
bytes of data
Note: The power supply will not return the response command after receiving the software reset command.
2. Instructions
Opcode
Function
Description
the data shows
Meaning of
reading data
Write data meaning
0x30
Output
status
byte
Whether the current is overloaded
1 :
Current
overload
0 :
normal
0 :
clear current overload
sign
Byte
1
Power failure alarm
1 :
Power failure
0 :
normal
1:
Reset to clear the
alarm mark
Byte
2
Is it currently in high-end or low-end
1:
high-end
0:
low gear
be ignored
Byte
3
Whether to output
1:
output
0 :
No output
be ignored
0x31
Target
frequency
Frequency value of
4
bytes, unit
0.1 H
B
range
450-1200
Current
frequency value
Updated frequency value
0x32
High-end
target
voltage
4
-byte value of the voltage, the unit
of 0.
The 1V,
range
0-3000
Current voltage
value
The updated voltage
value, if it was low gear
before, it will also switch
to high gear
0x33
Automatic
target
voltage
4
-byte value of the voltage, the unit
of 0.
The 1V,
range
0-3000
Current voltage
value
The updated voltage
value will switch between
high and low gears
according to the value of
the set voltage. The
standard for the switch is:
set the voltage to
1500
to
upshift, otherwise low
Summary of Contents for APS-4000 Series