Display
Summary of function
dEbounCE
[for Input-b]
Defines
level of input debounce
applied to the pulse input b to prevent
false counting:
dEFAuLt
HEAVY
LiGHt
See section 5.9
CntEdG-A
Input A pulse counting edge
Defines whether the Counter is
incremented/decremented on the
leading or trailing edge of a pulse on
input A.
See section 5.10
CntEdG-b
Input b pulse counting edge
Defines whether the Counter is
incremented/decremented on the
leading or trailing edge of a pulse on
input b.
See section 5.11
updAtE
Display update interval
Defines the interval between display
updates between 0.5 and 5 seconds.
See section 5.12
Count
Counting function
Defines the arithmetic relationship of
the two pulse inputs. The total
display can be derived from:
A:b
Input A + Input b
A:-b
Input A - Input b
A con b
Input A controlled by
Input b.
a rel b
Quadrature input
(for position display)
See section 5.13
di5P-1
Upper display
Defines whether
rAtE
or
totAL
is
shown on the upper display. The
other variable will be shown on the
lower display, providing the lower
display is
on
in function
dI5P-2
.
See section 6.14
Display
Summary of function
di5P-2
Lower display
Turns the lower display, which
normally shows rate,
on
or
oFF
.
See section 5.15
dP
Position of decimal points
Defines the position of the decimal
point in both the total and rate
displays.
See section 5.16
5CALE
.
t
Total Scale Factor
5CALE
.
t
is a dividing factor that
converts the pulse output from
arithmetic
Count
function into the
required total display in
engineering units.
5CALE
.
t
may
be adjusted between. 0.0001 and
99999. e.g. if one pulse
represents 1 centimetre of
dispensed cable and the total
display is required in metres,
5CALE
.
t
should be set to 100.0
which is the number of centimetres
in a metre.
The total display is independent of
the rate display.
See section 5.17
5CALE
.
r
Rate scale factor
5CALE
.
r
is a dividing factor that
converts the pulse output from the
arithmetic
Count
function into the
required rate display in
engineering units.
5CALE
.
r
may
be adjusted between 0.0001 and
99999.
e.g. if one pulse
represents 2 pump strokes and the
rate display is required in pump
strokes,
5CALE
.
r
should be set to
0.5.
The rate display is independent of
the total display.
See section 5.18
t-bA5E
Timebase
Selectable multiplier allowing rate
to be displayed in units per
second, per minute or per hour.
Select:
tb-01
for rate / second
tb-60
for rate / minute
tb-3600
for rate / hour
See section 5.19