22
www.coolautomation.com
CooLinkHub PRM 1.0
© 2017 CoolAutomation
ASCII I/F
EXAMPLE
Set operation mode of the indoor unit 102 on Line L1 to auto
>
auto L1.102
OK
Set operation mode of all indoor units on Line L2 to auto
>
auto L2*
OK
Set operation mode of all indoor units to auto
>
auto
OK
5.3.10 haux
SYNOPSIS
haux [
DESCRIPTION
Set operation mode of the ThermoPad device(s) connected to PBUS line of CooLinkHub to auxiliary heat
mode.
EXAMPLE
Set operation mode of the ThermoPad 083 on Line L2 to haux
>
haux L2.083
OK
Set operation mode of all ThermoPad devices on Line L2 to haux
>
haux L2*
OK
5.3.11 temp
SYNOPSIS
temp [
] [±]<TEMP>
temp [
] <TEMP.d>
DESCRIPTION
Change indoor unit(s) Set Temperature.
·
In form
temp [UID] [±]<TEMP>
<TEMP>
parameter must be decimal natural number. Command can work in relative or absolute manner.
If plus '
+
' or minus '
-
' sign precedes
<TEMP>
parameter, it's value will be added to or substituted from the
current Set Temperature value. Otherwise Set Temperature will be set to the given
<TEMP>
value.
·
In form
temp [UID] <TEMP.d>
Set Temperature parameter
<TEMP.d>
is a fractal number with 0.1 precision. (In this case preceding
+
or
-
are not allowed). If HVAC system does not support 0.1 precision for the Set Temperature (see table
below), the final value will be the nearest supported value.