3-Phase Intelligent PDU User Guide
Firmware Upgrade
scp <filename> <user>@<
IP address of PDU>:
Note:
(5) The SSH setting on the PDU must be Enabled.
(6)
<filename>
is the filename of the firmware file. There are two firmware files to upload:
cpsmpdumbfw_XXX.bin
and
cpsmpdumbdata_XXX.bin
. In order to upgrade the firmware
version both files need to be uploaded. Only one firmware file can be uploaded at a time, it is
recommended to upload the firmware file
cpsmpdumbfw_XXX.bin
first followed by the data file
cpsmpdumbdata_XXX.bin
.
(7)
<user>
is the username of the SSH account on the PDU.
(8)
Ensure to add “
:
” after the IP address.
For example:
scp cpsmpdumbfw_XXX.bin cyber@192.168.1.100:
Note:
cpsmpdumbfw_XXX.bin
is the firmware file of the version being updated.
4. After executing the command, a message may appear asking if you trust the host. To continue type
"
y
” for yes within 10 seconds.
5. On the next screen enter the PDU password. The firmware file transfer may take a couple minutes
to complete. Please wait until the progress indicator displays 100%. The system will automatically
log out and reboot after the transfer is complete.
6. Repeat steps 3 through step 5 to upload the data file
cpsmpdumbdata_XXX.bin
to complete the
firmware update process.
7. If the firmware file transfer is unsuccessful you will see an error message. Attempt to retype the
command and execute it again.