41 - 70
71130/11E/0318
Command AT
<id>AT<para5>
Adjust the measuring range of the air temperature [°C] for analogue output.
Access:
Configuration mode (ADMIN).
Description:
This command is used to specify the output range for the air temperature.
Parameter description:
00APsxxyy
s : leading sign of lower temperature
xx: lower terminal value of temperature
yy: upper terminal value of temperature
00AP14060
Sets the measuring range of the temperature to -40...+60°C
00AP13070
Sets the measuring range of the temperature to -30...+70°C
Value range:
s
0..1
1 = negative leading sign
xx
0..50
yy
50..90
Initial value:
14060
output range -40°C..+60°C
Command AV
<id>AV<para5>
Averaging period
(Average).
Access:
User mode.
Description:
This command determines the period when the WEATHER STATION averages all
measuring values.
The wind measuring values are gliding-averaged, corresponding to WMO-regulation
acc. to the FIFO method. No gust is calculated for averaging times below 3s!
Parameter description:
Parameter for AV
Selected averaging time
0
No averaging
1
Averaging over 100ms
10..6000
Averaging over 1..600.0s
Table 8: Selection of averaging periods with parameter AV
The averaging memory is designed as a sliding memory.
On start-up the data of the averaging memory is instantly valid. Averaging is performed
immediately using the measured values available.
Value range:
0..6000
Initial value:
10
Command BO
<id>BO<para5>
Calculation method of the total brightness (Brightness Option).
Access:
Configuration mode (ADMIN).
Description:
Defines the calculation of the total brightness from the values of the 4 single sensors.
Parameter description:
0:
Greatest value of the four sensors.
1:
Vectorial sum from both adjacent sensors
with the maximum measured brightness.
Value range:
0..1
Initial value:
0