18
Parameter 145
–
Humidity Sensor Report Threshold
This Parameter determines the change in humidity level in % resulting in humidity sensors report being sent to the
gateway. From 1% to 25% can be selected. Use the value 0 if there is a need to stop sending the reports. The factory
default value is 2.
Note:
When the thermostat is turning ON, the sensor data will be sent to the gateway once, even if the value of this
Parameter is 0.
Note:
It is recommended not to decrease the value of this Parameter, in order not to increase the load on your Z-Wave
network traffic.
Parameter 146
–
Light Sensor Report Threshold
This Parameter determines the change in the ambient environment illuminance level resulting in a light sensors report
being sent to the gateway. From 10% to 99% can be selected. Use the value 0 if there is a need to stop sending the
reports. The factory default value is 50.
Note:
When the thermostat is turning On, the sensor data will be sent to the gateway once, even if the value of this
Parameter is 0.
Note:
It is recommended not to decrease the value of this Parameter, in order not to increase the load on your Z-Wave
network traffic.
Association Commands Action
Parameter 171
(“bSA”) –
Basic Set Action
This Parameter defines which Operating Mode the HE-HT01 reverts to if the Basic Set command is received. If the Basic
Set command value is 0 (OFF state) the HE-HT01 will go to Manual (MAN) mode and switch Off the heating element
(IDLE mode). If the Basic Set command is value is 0xFF (ON state) the HE-HT01 will change the Mode to the
corresponding Parameter value (as follows):
0: No action (ignoring Basic Set commands)
1: COM Mode
2: TIME Mode
3: DRY Mode
4: ECO Mode
5: VAC Mode
6: MAN Mode with HEATING state
The factory default value is 1.
Factory Default Parameters
Number
Size
Description
Default
Value
Available
Values
1
1 byte
Frequency Region
Read Only
0 … 9
2
1 byte
Inclusion / Exclusion Mode
Read Only
0, 1
3
4 bytes
Hardware and Software Versions
Read Only
XXYYZZ
4
4 bytes
Energy Consumption, kW
Read Only
Total consumption
5
1 byte
Display brightness control
0
0, 1 … 10
6
1 byte
Touch buttons sensitivity. 1 = Lowest; 10 = Highest
6
1 … 10
7
1 byte
Relay output NO or NC mode
0
0, 1
8
1 byte
External input mode
0
0, 1, 2, 3
9
1 byte
Mode number for external input action
6
1, 2, 3, 4, 5, 6
10
1 byte
Floor Sensor Resistance, kΩ
10
1 … 100
11
1 byte
Source Sensor: 1=A, 2=AF, 3=F, 4=FA, 5=t, 6=tA, 7=tF
3
1, 2, 3, 4, 5, 6, 7
12
2 bytes
Air Temperature Minimum in °C, value X 10, e.g. 21.5°C=215
210
10 … 360
13
2 bytes
Air Temperature Maximum in °C, value X 10, e.g. 27.0°C=270
270
20 … 370
14
2 bytes
Floor Temperature Minimum in °C, value X 10, e.g. 18.0°C=180
180
10 …
360
15
2 bytes
Floor Temperature Maximum in °C, value X 10, e.g. 32.0°C=320
320
20 … 370
16
1 byte
Floor Temperature Calibration in °C, value X 10, e.g. 1.5°C=15
0
-
100 … 100