4 Start-up
X-AI 32 51
Page 36 of 58
HI 801 181 E Rev. 4.00
4.3.2
Tab: I/O Submodule AI32_01
The
I/O Submodule AI32 01
tab contains the following system parameters:
Name
R/W
Description
Enter these statuses and parameters directly in the Hardware Editor.
Name R
Module
name
Supply ON
W
Use the transmitter supplies of the module.
Activated: Transmitter supplies for channels 1 to 32
activated.
Deactivated: Transmitter supplies for channels 1 to 32
deactivated.
Default setting: Activated
Show Signal Overflow
W
The
Field
LED displays a potential signal overflow.
Activated: Show signal overflow activated.
Deactivated: Show signal overflow deactivated
Default setting: Activated
Name
Data
Type
R/W
Description
The following statuses and parameters can be assigned global variables and used in the user program.
Background Test Error
BOOL
R
TRUE: Background test is faulty
FALSE: Background test is free of faults
Diagnostic Request
DINT
W
To request a diagnostic value, the appropriate ID must be
sent to the module using the parameter
Diagnostic
Request
(see Chapter 4.3.5 for coding details).
Diagnostic Response
DINT
R
As soon as
Diagnostic Response
returns the ID of
Diagnostic Request
(see 4.3.5 for coding details),
Diagnostic Status
contains the diagnostic value
requested.
Diagnostic Status
DWORD
R
Requested diagnostic value in accordance with
Diagnostic Response.
The IDs of
Diagnostic Request
and
Diagnostic Response
can be evaluated in the user program.
Diagnostic Status
only contains the requested diagnostic value when both
Diagnostic Request and Diagnostic Response have the
same ID.
Restart on Error
BOOL
W
Using the parameter
Restart on Error
, each I/O module
that has switched off permanently due to faults can be
forced to re-adopt the RUN state. To do this, set the
Restart on Error
parameter FALSE to TRUE.
The I/O module performs a complete self-test and only
enters the RUN state if no faults are detected.
Default setting: FALSE
Submodule OK
BOOL
R
TRUE: No submodule fault.
No channel faults.
FALSE: Submodule fault.
Channel fault (external faults included)
Submodule Status
DWORD
R
Bit-coded submodule status
(For coding details, see Chapter 4.3.4)
Table 22: Tab: I/O Submodule AI32_01 in the Hardware Editor