Function Block Objects & Sub-Parameters
The following is an overview of the function block features and options. For in-depth description of
function choices and their use please also download or request the separate
FUNCPROG Application
Tool
document.
Function Block
Object
Para #
Description
Selection Options
Digital Input 1…8
1…8
x00=
x01=
x02=
Input type
Output OR
Output AND
6 - Pulse counting, 7 - Digital, 14 - n/c, 15
- Toggle on/off
Object #
Object #
Digital Output 1…8
9…16
(x)x06=
(x)x07=
(x)x08=
Minimum ON time (sec)
Minimum OFF time (sec)
Maximum Run time (sec)
0…255
0…255
0…1000
Universal Input 1…8
17…24
xx00=
Sensor type
0 - 100k NTC (-10…90°C)
[Ctc]
1 - Ni1000 (-10…90°C)
[Cni]
2 - 0-10Vdc (0…100%)
[%V1]
3 - 4…20mA (0…100%)
[%mA]
4 - PT1000 (-10…90°C)
[Cpt]
5 - 10k NTC (-10…90°C)
[Ctx]
6 - Pulse counter
[P]
7 - Digital
[D]
8 - % (0-100%)
[%]
9 - Seconds
[Sec]
14 - Digital normally-closed
[DNC]
15 - Toggle on/off
[D T]
xx01=
Input calibration - Offsets the
measured value up to 10% of the
sensor range
Any value /-10% of the sensor
range
xx02=
Filter incoming sensor measurement
when the connected sensor is
unstable
0 - Minimum (factory default)
1…9 - User setting where 9 represents
the maximum filtering sample time
For unstable sensors then a setting of 1
or 2 will typically be enough filtering to
result in a stable measurement
xx03=
xx04=
Output OR*
Output AND*
Object #
Object #
Analogue Output 1…4
25…28
* Digital 1 = 1000 (100%) when applied to these analogue logic functions. Analogue values will act as a
Output Minimum when applied to an Output OR and Output Maximum when applied to an Output AND.