background image

 

PM

-

3133 User

’s Manual v1.09   

 

  Last Revised: Jun. 2021                                          Page: 39   

Copyright ©  ICP DAS Co., Ltd.    All Rights Reserved.   

www.icpdas.com

         

 E-mail: service@icpdas.com

 

2: initiate upload request 

scs

: server command specified 

2: initiate upload response 

: Only valid if 

= 1 and 

= 1, otherwise 0.   

If valid, it indicates the number of bytes in 

that do not contain data. Bytes [8-

n

, 7] 

do not contain segment data. 

e

: transfer type 

0: normal transfer 

1: expedited transfer 

If the 

e

=1, it means that the data of the object are equal or less than 4 bytes, and 

only  initiate  SDO  upload  protocol  is  needed.  If 

e

=0,  the  upload  SDO  segment 

protocol is necessary. 

s

: size indicator 

0: Data set size is not indicated. 

1: Data set size is indicated. 

m

: multiplexer 

It  represents  the  index/sub-index  of  the  data  to  be  transfer by  the SDO.  The first 

two bytes are the index value and the last byte is the sub-index value. 

d

: data 

e

=0, 

s

=0: 

is reserved for further use. 

e

=0, 

s

=1: 

contains the number of bytes to be uploaded, and byte 4 contains the 

least significant bit, and byte 7 contains the most significant bit. 

e

=1, 

s

=1: 

contains the data of length 4-

to be uploaded, the encoding depends 

on the type of the data referenced by index and sub-index. 

e

=1, 

s

=0: 

contains unspecified number of bytes to be uploaded. 

x

: not used, always 0 

reserved

: reserved for further use , always 0 

 

Upload SDO Segment Protocol 

When the upload data length is over 4 bytes, the upload SDO segment protocol will be 

needed.  After finishing  the  transmission of  the  initiate  SDO upload protocol, the  SDO 

client will start to upload the data. The upload SDO segment protocol will comply with 

the process shown below. 

Summary of Contents for PM-3133-MTCP

Page 1: ...PM 3133 User s Manual v1 09 Last Revised Jun 2021 Page 1 Copyright ICP DAS Co Ltd All Rights Reserved www icpdas com E mail service icpdas com...

Page 2: ...nspection 10 3 2 Safety 10 3 2 1 Dimension and Latch 10 3 2 2 Mounting and Dismounting 12 3 2 3 CT s installation steps 13 Chapter 4 Wiring Diagrams 14 4 1 Connection 14 4 2 Wiring 16 5 1 Relay 18 5 2...

Page 3: ...tocol 44 8 2 2 PDO Introduction 46 8 2 2 1 PDO COB ID Parameters 46 8 2 2 2 Transmission Type 47 8 2 2 3 PDO Communication Rule 48 8 2 3 NMT Introduction 50 8 2 3 1 Module Control Protocol 50 8 2 3 2...

Page 4: ...e and accurate energy consumption readings from the monitored equipments while in operation These compact size and cost effective Power Meters are equipped with revolutionary wired clip on CT various...

Page 5: ...resulting from the use of this product ICP DAS reserves the right to change this manual at any time without notice The information furnished by ICP DAS is believed to be accurate and reliable However...

Page 6: ...Rights Reserved www icpdas com E mail service icpdas com 1 4 1 Limitation of Warranty This warranty does not apply to defects resulting from unauthorized modification misuse or use for reason other t...

Page 7: ...05A 100A 0 09A 200A Power Parameter Measurement True RMS voltage Vrms True RMS current Irms Active Power kW Active Energy kWh Apparent Power kVA Apparent Energy kVAh Reactive Power kVAR Reactive Ener...

Page 8: ...26 AWG torque value 3 0 lb in 5 08mm For Measurement Voltage Aux Power and Alarm Output Use Copper Conductors Only wires range 12 24 AWG torque value 7 0 lb in 7 62mm Use Copper Conductors Only wires...

Page 9: ...PM 3133 User s Manual v1 09 Last Revised Jun 2021 Page 9 Copyright ICP DAS Co Ltd All Rights Reserved www icpdas com E mail service icpdas com 2 2 Naming Rules...

Page 10: ...he instrument is no longer safe when a Shows clear signs of damage b Does not work c Long storage under extreme conditions d Damage during shipment 3 2 Safety Please use the soft dry clothes to clean...

Page 11: ...plit type clip on CT s Disconnect the CT s or use other CT s is highly prohibited Please read this operation manual carefully before using Please re confirm the measure position PM 3133 series can be...

Page 12: ...Disconnection 1 Open the CT clip to detach the CT do not remove the CT terminal lines if possible Note if you need to remove the terminal lines always detach the CT before removing the CT terminal lin...

Page 13: ...Ltd All Rights Reserved www icpdas com E mail service icpdas com 3 2 3 CT s installation steps At the bottom of the CT there is a K L mark Open the CT clip Make sure the power current direction follow...

Page 14: ...te black white black white black wire sequences CT1 K CT1 L CT2 K CT2 L CT3 K CT3 L Then connect the CT s and close the CT clip Make sure the arrow direction sign on CT s follows current flow directio...

Page 15: ...each set of smart meter PM 3133 series and its attached split type clip on CT are calibrated set by set The mix use may cause wrong measurements 4 To install CT s correctly please ensure the CT lines...

Page 16: ...3133 User s Manual v1 09 Last Revised Jun 2021 Page 16 Copyright ICP DAS Co Ltd All Rights Reserved www icpdas com E mail service icpdas com 4 2 Wiring 1P2W 1CT PM 3133 1P3W 2CT PM 3133 3P3W 2CT PM 31...

Page 17: ...PM 3133 User s Manual v1 09 Last Revised Jun 2021 Page 17 Copyright ICP DAS Co Ltd All Rights Reserved www icpdas com E mail service icpdas com 3P3W 3CT PM 3133 3P4W 3CT PM 3133...

Page 18: ...oltage Range 250 VAC 30 VDC Max Load Current 5 A at 25 C Operate Time 6 ms Release Time 3 ms 5 2 LED Indicator The PM 3133 has 4 LED to indicate the unit power status RS 485 communication and power da...

Page 19: ...s SW 1 SW 2 SW 3 SW 4 SW 5 SW 6 1 OFF OFF OFF OFF OFF OFF 2 ON OFF OFF OFF OFF OFF 3 OFF ON OFF OFF OFF OFF 4 ON ON OFF OFF OFF OFF 5 OFF OFF ON OFF OFF OFF 6 ON OFF ON OFF OFF OFF 7 OFF ON ON OFF OFF...

Page 20: ...ON 39 OFF ON ON OFF OFF ON 40 ON ON ON OFF OFF ON 41 OFF OFF OFF ON OFF ON 42 ON OFF OFF ON OFF ON 43 OFF ON OFF ON OFF ON 44 ON ON OFF ON OFF ON 45 OFF OFF ON ON OFF ON 46 ON OFF ON ON OFF ON 47 OFF...

Page 21: ...bps ON ON Add the Bias Resistor on RS 485 Network for stable signal The RS 485 master is required to provide the bias for PM 3133 series Otherwise the tM SG4 or SG 785 should be added to provide the b...

Page 22: ...Read Coils Read boolean values of read write location 05h Write Single Coil Set one boolean value of read write location 0Fh Write Multiple Coil Set boolean values of read write location 03h Read Hold...

Page 23: ...itive E is the two s complement exponent with an offset of 127 i e an exponent of zero is represented by 127 an exponent of 1 by 128 etc M is the 23 bit normal mantissa The highest bit is always 1 and...

Page 24: ...Modbus Module 2 Holding Register System Parameter Setting Parameter name Modbus Register Len Data Type Range Default value Units Comment Modicom Format Hex PT_Ratio 44100 0x1003 Word UInt 1 65535 100...

Page 25: ...t Register System Information Parameter name Modbus Register Len Data Type Range Default value Units Comment Modicom Format Hex Wiring Type 30513 0x0200 Word UInt 9 1P2W 10 1P3W 11 3P3W2CT 12 3P3W3CT...

Page 26: ...kW_b 34375 34376 0x1116 0x1117 DWord Float kW kvar_b 34377 34378 0x1118 0x1119 DWord Float kvar kVA_b 34379 34380 0x111A 0x111B DWord Float kVA PF_b 34381 34382 0x111C 0x111D DWord Float kWh_b 34383...

Page 27: ...0 1A kW_a 34613 34614 0x1204 0x1205 DWord Int32 0 1kW kvar_a 34615 34616 0x1206 0x1207 DWord Int32 0 1kvar kVA_a 34617 34618 0x1208 0x1209 DWord Int32 0 1kVA PF_a 34619 0x120A Word Int 0 1000 0 001PF...

Page 28: ...74 0x1240 0x1241 DWord Int32 0 99999999 0 1kvarh 0 9999999 9 kVAh_tot 34675 34676 0x1242 0x1243 DWord Int32 0 99999999 0 1kVAh 0 9999999 9 Freq_a 34677 0x1244 Word Int 45 65 1Hz 45 65 Freq_b 34678 0x1...

Page 29: ...2C Word Int 0 1000 0 001PF 0 1 000 kWh_c 34910 34911 0x132D 0x132E DWord Int32 0 99999999 0 1kWh 0 9999999 9 kvarh_c 34912 34913 0x132F 0x1330 DWord Int32 0 99999999 0 1kvarh 0 9999999 9 kVAh_c 34914...

Page 30: ...SW 4 to Init position for 10 seconds after power on the settings will be changed as default values Must dip back to Run position and repower on after settings changed User also can recover settings to...

Page 31: ...Revised Jun 2021 Page 31 Copyright ICP DAS Co Ltd All Rights Reserved www icpdas com E mail service icpdas com Click Search to enter the Communication Interface Setting window Click Search button to...

Page 32: ...Ltd All Rights Reserved www icpdas com E mail service icpdas com Select the power meter which you want to modify parameters from the meter list then click Configuration button to setup the meter param...

Page 33: ...saction identifier Protocol identifier Data length upper byte Data length lower byte Transaction identifier Assign by Modbus TCP Master Client Protocol identifier 0 Data length upper byte 0 Data lengt...

Page 34: ...pdas com E mail service icpdas com 7 3 Connecting the Power and Host PC without PoE Power over Ethernet PoE The PM 3133 xxx MTCP module can be powered by an IEEE802 3af compliant PoE switch Both Ether...

Page 35: ...5 SW 6 1 OFF OFF OFF OFF OFF OFF 2 ON OFF OFF OFF OFF OFF 3 OFF ON OFF OFF OFF OFF 4 ON ON OFF OFF OFF OFF 5 OFF OFF ON OFF OFF OFF 6 ON OFF ON OFF OFF OFF 7 OFF ON ON OFF OFF OFF 8 ON ON ON OFF OFF O...

Page 36: ...ON 40 ON ON ON OFF OFF ON 41 OFF OFF OFF ON OFF ON 42 ON OFF OFF ON OFF ON 43 OFF ON OFF ON OFF ON 44 ON ON OFF ON OFF ON 45 OFF OFF ON ON OFF ON 46 ON OFF ON ON OFF ON 47 OFF ON ON ON OFF ON 48 ON ON...

Page 37: ...tting PM 3133 For CANopen Baud Rate Setting Baud Rate SW 7 SW8 125 K bps Default OFF OFF 250 K bps ON OFF 500 K bps OFF ON 1M bps ON ON SW9 SW10 setting PM 3133 CPS Select the different wiring mode Pl...

Page 38: ...SDO segments the client and server need to communicate with each other by using the initiate SDO upload protocol Via the initiate SDO upload protocol the SDO client will inform the SDO server what ob...

Page 39: ...represents the index sub index of the data to be transfer by the SDO The first two bytes are the index value and the last byte is the sub index value d data e 0 s 0 d is reserved for further use e 0...

Page 40: ...ded seg data It is at most 7 bytes of segment data to be uploaded The encoding depends on the type of the data referenced by index and sub index n It indicates the number of bytes in seg data that do...

Page 41: ...and only initiate SDO download protocol is needed If e 0 the download SDO segment protocol is necessary s size indicator 0 Data set size is not indicated 1 Data set size is indicated m multiplexer It...

Page 42: ...3133 User s Manual v1 09 Last Revised Jun 2021 Page 42 Copyright ICP DAS Co Ltd All Rights Reserved www icpdas com E mail service icpdas com x not used always 0 reserved reserved for further use alway...

Page 43: ...erenced by index and sub index n It indicates the number of bytes in seg data that do not contain segment data Bytes 8 n 7 do not contain segment data n 0 if no segment size is indicated c It indicate...

Page 44: ...s that users want to modify does not exist or is read only even users wouldn t continue the uncompleted SDO protocol under some special situations When these conditions occur both the client and the s...

Page 45: ...4 0047h General internal incompatibility in the device 0606 0000h Access failed due to a hardware error 0607 0010h Data type does not match length of service parameter does not match 0607 0012h Data t...

Page 46: ...g is given in the table follow Bit Number Value Meaning 31 MSB 0 PDO exits PDO is valid 1 PDO does not exist PDO is not valid 30 0 RTR allowed on this PDO 1 No RTR allowed on this PDO 29 0 11 bit ID C...

Page 47: ...table describes the relationship between the value of the transmission type and the PDO character For example if users used transmission type 0 for the first TxPDO the CANopen device will follow the r...

Page 48: ...ex 0x1800 and the corresponding mapping object is stored in an entry with index 0x1A00 The object with index 0x1801 and the object with index 0x1A01 are a group and so on Therefore before users access...

Page 49: ...Ltd All Rights Reserved www icpdas com E mail service icpdas com COB ID the default PDO COB ID or the PDO COB ID defined by users L the data length about how many bytes the PDO message has PDO msg th...

Page 50: ...ntrol Protocol The NMT communication set can be applied for changing the NMT slave status The following figure shows how to change the different NMT statuses for the PM 3133 CPS Start Remote Node Prot...

Page 51: ...Rights Reserved www icpdas com E mail service icpdas com Enter Pre Operational Protocol cs NMT command specified 128 enter PRE OPERATIONAL Node ID the node ID of the NMT slave device Reset Node Protoc...

Page 52: ...s related objects include 0x100C and 0x100D The 0x100C is the guard time and the 0x100D is the life time factor The node life time is the guard time multiplied by the life time factor The Node Guardin...

Page 53: ...00 0x3209 will map to the PDOs as below table The D0 to D7 represent the CANopen message from Data0 to Data7 No PDO COB ID Data Length D0 D3 D4 D7 1 0x180 Node ID 8 kW Kw_a kWh_a 2 0x280 Node ID 8 kW...

Page 54: ...built in PM 3133 CPS In the table the number accompanying letter h indicates that this value is in the hex format General Communication Entries Idx Sidx Description Type Attr Default 1000h 0h device...

Page 55: ...Description Type Attr Default 1200h 0h largest sub index supported for server SDO parameter UNSIGNED 8 RO 2 1h COB ID form client to server RxSDO UNSIGNED 32 RO 600h Node ID 2h COB ID form server to c...

Page 56: ...IGNED 16 RW 0 4 reversed 5 event timer UNSIGNED 16 RW 0 1804h 0 largest sub index supported for receive PDO parameter UNSIGNED 8 RO 5 1 COB ID used by PDO Tx UNSIGNED 32 RW 80000000h 2 transmission ty...

Page 57: ...read V_a data UNSIGNED 32 RW 3202 0120h 2 read I_a data UNSIGNED 32 RW 3203 0120h 1A05h 0 largest sub index supported for transmit PDO mapping UNSIGNED 8 RO 2 1 read V_b data UNSIGNED 32 RW 3202 0220h...

Page 58: ...2 1 read PF_b data UNSIGNED 32 RW 3206 0220h 2 read kVAh_b data UNSIGNED 32 RW 3207 0220h 1A0Eh 0 largest sub index supported for transmit PDO mapping UNSIGNED 8 RO 2 1 read PF_c data UNSIGNED 32 RW...

Page 59: ...ic Profile Area In the following table there is information about some special functions for the PM 3133 CPS The index from 0x3200 to 0x3209 records the power meter measurement parameters The number o...

Page 60: ...L 32 RO 0 3204h 0 Number of entries for kvar UNSIGNED 8 RO 4 1 kvar kvar_a REAL 32 RO 0 2 kvar kvar_b REAL 32 RO 0 3 kvar kvar_c REAL 32 RO 0 4 kvar kvar_tot REAL 32 RO 0 3205h 0 Number of entries for...

Page 61: ...2 RO 0 320Bh 0 Number of entries for System Parameter Setting UNSIGNED 8 RO 6 1 PT Ratio UNSIGNED 16 RW 100 2 CT Ratio UNSIGNED 16 RW 1 3 Wiring Mode UNSIGNED 8 RW 5 4 Energy Absolute Accumulated Mode...

Page 62: ...or write the value 64616F6Ch to object with index 1011h and subindex 1 and reboot the module to load the factory default The following table lists the relative objects which will be stored or restored...

Page 63: ...equipments before the CT lines detach from the terminals of the smart meter Otherwise it will cause the severe injury Q3 If the turn point of the split type clip on CT has broken or inner Ferrite cor...

Page 64: ...provide the bias for PM 3133 series Otherwise the tM SG4 or SG 785 should be added to provide the bias All ICP DAS controllers and converters provide the bias Q7 What the power cable diameter mm of th...

Page 65: ...PM 3133 maximum range is 400A If the target is more than 400A we suggest the solution as follow For example the target is to measure maximum 800A current We can measure big CT output and set a CT Rati...

Page 66: ...12 1 800A CT 160 1 100A CT 20 1 1000A CT 200 1 200A CT 40 1 1200A CT 240 1 Note A Please use low phase angle error CTs essential for accurate power and energy measurements Example phase error 2 B Pri...

Page 67: ...PM 3133 User s Manual v1 09 Last Revised Jun 2021 Page 67 Copyright ICP DAS Co Ltd All Rights Reserved www icpdas com E mail service icpdas com voltage is 380 1 73 220 volts...

Page 68: ...ired to set different Display Voltage value If the voltage is not displayed as expected value please refer to the table below and check if the setting value is set accurately Line to Ground Voltage Li...

Page 69: ...on the supply voltage available at your facility Example PRI Voltage 720V SEC Voltage 120V Check the connection diagram three phase Y and delta phase sequence to ensure compatibility Adding potential...

Page 70: ...tSH 735 This function allows two master devices connected to different serial ports to share slave devices Modbus mode can be used to convert the Modbus RTU ASCII protocols while raw data mode can be...

Page 71: ...IZE mm2 Quantity Diameter mm Flat cable 1 6 3 2 15 10 PM 3133 100 10mm 60A 2 0 3 6 20 Twisted pair 2 0 7 0 6 3 4 17 3 5 7 0 8 4 0 20 5 5 7 1 0 5 0 30 8 0 7 1 2 6 0 40 14 7 1 6 7 6 55 22 7 2 0 9 2 70 1...

Reviews: