D - 8
Appendix
D.5. Hierarchy error (failure #9)
Program calls and other module calls must not exceed certain
hierarchy limits (see chapter "4.7. Module programming").
During programming, the controller reports a hierarchy error
when it receives a program. At this stage, this is only a warning
that there could be an error. Only at start-up does the controller
check whether there is really a hierarchy error. If there is not,
the error indication disappears again.
Cause
When switching the controller on or after the KUBES start com-
mand
,
the monitor program checks whether there is a hierarchy
error (a module calls up the module by which itself was called
up or the nesting depth exceeds 5 levels)
Reaction
the controller does not start
Indication
"failure" LED flashes
"Stop" LED is on
Error byte "ERR00.00" is set to 9
Remedy
determine the cause of the error and remove it
use the Transmit command of the KUBES PLC menu to
tansmit the project again to the controller