e
Electro Industries/GaugeTech
Doc # E134-7-15 V1.01
12-3
n
Operation Indicator (0000H = OK, 1000H = Problem)
•
Bit 1:
1 = EEPROM Failure
•
Bit 2:
1 = Checksum for Communications Settings bad
•
Bit 3:
1 = Checksum for Programmable Settings bad
•
Bit 4:
1 = 1 or more Communications Settings are invalid
•
Bit 5:
1 = 1 or more Programmable Settings are invalid
•
Bit 6:
1 = 1 or more Programmable Settings have been modified
•
Bit 7:
1 = Forced Default by Reset Switch
•
Bit 15:
1 = Normal Operation of the device is disabled
12.4.1: Channel Last/Next Energy, Channels 1-4
12.4.1: Channel Last/Next Energy, Channels 1-4
n
Registers 04097-04112 (0x01000-0x01000F)
Energy readings are written to these registers. The reading is an 8-byte value. The range is
18,446,744,073,709,551,615 / 0.
The Master Device continuously writes energy readings to these registers. New readings will over-
write the old readings. The difference between old readings and new readings will be added to the
Channel Residual Energy registers.
12.4.2: Channel Residual Energy, Channels 1-4
12.4.2: Channel Residual Energy, Channels 1-4
n
Registers 04113-04128 (0x01010-0x0101F)
When the new energy readings are different from the old readings, the difference will be added to
these registers. The reading is also an 8-byte value. The range is 18,446,744,073,709,551,615 / 0.
If the number in these registers is larger than or equal to the number in the Channel Energy/Pulse
registers, the number in the Channel Residual Energy registers will decrease by the number in the
Channel Energy/Pulse registers until the number in the Channel Residual Energy registers becomes
smaller than the number in the Channel Energy/Pulse registers. When the number in the Channel
Residual Energy registers decreases, the number in the Channel Pending Pulse registers will
increment.
12.4.3: Channel Pending Pulse, Channels 1-4
12.4.3: Channel Pending Pulse, Channels 1-4
n
Registers 04129-04132 (0x01020-0x01023)
These registers update the number of pulses to be sent out to each channel. The reading is a 2-byte
value and the range is 65535 / 0.
The number will decrement when a pulse is generated at the output.
12.4.4: Channel Energy/Pulse, Channels 1-4
12.4.4: Channel Energy/Pulse, Channels 1-4
n
Registers 45073-45080 (0x0B010-0x0B017)
These registers contain the energy readings per pulse. The reading is a 4-byte value and the range is
Summary of Contents for I/O Module
Page 2: ......
Page 6: ...e Electro Industries Gauge Tech Doc E134 7 15 V1 01 iv ...
Page 10: ...e Electro Industries Gauge Tech Doc E134 7 15 V1 01 viii ...
Page 30: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 2 16 ...
Page 44: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 4 8 ...
Page 50: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 6 4 ...
Page 52: ...e Electro Industries Gauge Tech Doc E 134 7 15 V1 01 7 2 ...
Page 63: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 8 4 ...
Page 65: ...e Electro Industries Gauge Tech Doc E 134 7 15 V1 01 9 2 ...
Page 72: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 10 4 ...
Page 74: ...e Electro Industries Gauge Tech Doc E 134 7 15 V1 01 11 2 ...
Page 81: ...e Electro Industries Gauge Tech Doc E 134 7 15 V1 01 13 2 ...
Page 87: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 14 4 ...
Page 89: ...e Electro Industries Gauge Tech Doc E 134 7 15 V1 01 15 2 ...