modbus
vacon
• 27
24-hour s358 (0)40 8371 150 • Email: vacon@vacon.com
6
6.2.3.1
Control word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
-
-
-
-
-
-
-
-
-
-
-
-
-
RST
DIR
RUN
In Vacon applications, the three first bits of the control word are used to control the frequency con-
verter. However, you can customise the content of the control word for your own applications because
the control word is sent to the frequency converter as such.
Bit
Description
Value = 0
Value = 1
0
Stop
Run
1
Clockwise
Counterclockwise
2
Rising edge of this bit will reset active fault
3….15
Not in use
Not in use
Table 13. Control word bit descriptions
6.2.3.2
Speed reference
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
MSB
LSB
This is the Reference 1 to the frequency converter. Used normally as Speed reference.
The allowed scaling is –10000...10000. In the application, the value is scaled in percentage of the fre-
quency area between the set minimum and maximum frequencies.
6.2.3.3
Process data in 1 to 8
Process Data In values 1 to 8 can be used in applications for various purposes. Update rate is 10 ms
for all values. See Vacon NX Application Manual for usage of these data values.
6.2.4
Process data out
This register range is normally used to fast monitoring of the frequency converter.
Process data out
is
located in range ID 2101…2199. See Table 14.
ID
Modbus register
Name
Range/Type
2101
32101, 42101
FB Status Word
Binary coded
2102
32102, 42102
FB General Status Word
Binary coded
2103
32103, 42103
FB Actual Speed
0…10000 %
2104
32104, 42104
FB Process Data Out1
See appendix 1
2105
32105, 42105
FB Process Data Out2
See appendix 1
2106
32106, 42106
FB Process Data Out3
See appendix 1
2107
32107, 42107
FB Process Data Out4
See appendix 1
2108
32108, 42108
FB Process Data Out5
See appendix 1
2109
32109, 42109
FB Process Data Out6
See appendix 1
2110
32110, 42110
FB Process Data Out7
See appendix 1
2111
32111, 42111
FB Process Data Out8
See appendix 1
Table 14. Fieldbus basic output table