J DF 3 0 0 |
FI EL D I N D I C ATO R | O I/J D F 3 0 0 - EN R E V. B
23
HMI TB Mapping
Idx
Parameter
Description / Range / Selections / Notes
0
BLOCK_OBJ
In the Block Object data structure, there are different items describing the block characteristics. Execution period,
Number of parameters in the block, the DD Revision, Profile Revision, View Objects characteristics and so on
1
ST_REV
The revision level of the Static data associated with the Function Block. The revision level is incremented each time a
static parameter value (S – under Storage) in the block is changed.
2
TAG_DESC
The user description of the intended application of the block
3
STRATEGY
The strategy field can be used to identify grouping of blocks. This data is not checked or processed by the block.
4
ALERT_KEY
The identification number of the plant unit. This information may be used in the host for sorting alarms, etc.
5
MODE_BLK
TARGET
AUTO / OOS
The selectable modes by the operator.
ACTUAL
//
The mode the block is currently in.
PERMITTED
AUTO / OOS
Allowed modes that the target may take on
NORMAL
AUTO
The common mode for the Actual.
6
BLOCK_ERR
This parameter reflects the error status associated with the hardware or software components associated with a
block. It is a bit string, so that multiple errors may be shown.
Bit 15 = Out of Service
7
UPDATE_EVT
This alert is generated by any change to the static data
8
BLOCK_ALM
The block alarm is used for all configuration, hardware, and connection failure or system problems in the block.
The cause of the alert is entered in the sub-code field. The first alert to become active will set the Active Status in
the status parameter. As soon as the Unreported status is cleared by the alert reporting task, another block alert
may be reported without clearing the Active Status, if the sub-code has changed
9
TRANSDUCER_DIRECTORY
Directory that specifies the number and starting indices of the transducers in the transducer block
10
TRANSDUCER_TYPE
Identifies the transducer type.
TN-016 –
65535 = Other
11
XD_ERROR
Transducer block error sub-code
12
COLLECTION_DIRECTORY
Directory that specifies the num, starting indices, and the DD items IDs of the data collections in each transd
within a transducer block
13
HMI_CONTRAST
Display Contrast 0 to 100
Default [50]
14
HMI_LANGUAGE
0:
English (default)
1:
Deutch
2:
Francais
3:
Espanol
4:
Italiano
14:
Portuguese
15
HMI_MODE
5:
One Line
FIXED SELECTION
16
HMI_SW_REV
0:
Not Installed
xxx
Display SW Revision
17
IN1_SUBTAG
Default string:
“Input 1”
18
IN1_UNIT CODE
“********”
19
IN2_SUBTAG
Default string:
“Input 2”
20
IN2_UNIT CODE
“********”
21
IN3_SUBTAG
Default string:
“Input 3”
22
IN3_UNIT CODE
“********”
23
IN4_SUBTAG
Default string:
“Input 4”
24
IN4_UNIT CODE
“********”
25
IN5_SUBTAG
Default string:
“Input 5”
26
IN5_UNIT CODE
“********”
27
IN6_SUBTAG
Default string:
“Input 6”
28
IN6_UNIT CODE
“********”
29
IN7_SUBTAG
Default string:
“Input 7”
30
IN7_UNIT CODE
“********”