Log Strings
Interfacing Voyage Data Recorder Systems, AutroSafe Interactive Fire-Alarm System, 116-P-BSL336/EE, RevA 2007-01-25,
Autronica Fire and Security AS
Page 27
•
Type codes can be “PT” for Detector Point, or “FP” for a door
(FP for Fire Protection Equipment)
•
The number is incremented for each new unit added in the
AutroSafe configuration and carries no information except as
a unique reference.
The UnitId is very important in a situation where a VDR log event is
cross-referenced back into the Fire-Alarm System. The UnitId
information is placed in the indicator/number fields.
A UnitId example: PT12345 is laid out as
...,PT,012,345, ...
Field no
Data form Field name
Use
4
aa
Division indicator (1)
UnitId.Type:
Formatted as two alphabetic
characters.
See next table for a
complete list.
("PT" in the example)
5
xxx
Division indicator (2)
UnitId.Number (MSD)
Formatted as three numeric
characters.
The two most significant digits
(12 in the example) with a leading
zero
6
xxx
Door number or
Fire detector
number
UnitId.Number (LSD)
Formatted as three numeric
characters.
The three least significant digits
(345 in the example)
8.1.2.1 Overview of Unit Types (Division Indicator (1)) — Physical Units
and Zones
Unit type
Code Valid range
Point (smoke/heat/gas detectors)
PT
0x0-0x7ffc
Detection zone (groups of points)
DZ
0x0-0x3ffc
Fire alarm device (bells, sounders)
FD
0x0-0x7fc
Fire protection equipment (doors, fans, etc.)
FP
0x0-0x7fc
Alarm zone (groups of bells)
AZ
0x0-0x3fc
Detector loop
DL
0x0-0x3fc
Basic loop
BQ
0x0-0xfc
Computer
CO
0x0-0xfc
Domain network
DO
0x0-0xfc
Operator panel
OP
0x0-0x1fc
Power
PW
0x0-0xfc
Operation zone (DZs and AZs handled by an operator panel) OZ
0x0-0xfc
Unit Group
GR
0x0-0xfc
Panel
PA
0x0-0xfc