Commissioning
EL33xx-00x0
164
Version: 4.2
Index 1C32 SM output parameter
Index (hex) Name
Meaning
Data type
Flags
Default
1C32:0
SM output parameter
Synchronization parameters for the outputs
UINT8
RO
0x07 (7
dec
)
1C32:01
Sync mode
Current synchronization mode:
• 0: Free Run
• 1: Synchron with SM 2 Event
• 2: DC-Mode - Synchron with SYNC0 Event
• 3: DC-Mode - Synchron with SYNC1 Event
UINT16
RW
0x0000 (0
dec
)
1C32:02
Cycle time
Cycle time (in ns):
• Free Run: Cycle time of the local timer
• Synchron with SM 2 event: Master cycle time
• DC mode: SYNC0/SYNC1 Cycle Time
UINT32
RW
0x00000000
(0
dec
)
1C32:03
Shift time
Time between SYNC0 event and output of the outputs
(in ns, DC mode only)
UINT32
RW
0x00000000
(0
dec
)
1C32:04
Sync modes supported Supported synchronization modes:
• Bit 0 = 1: free run is supported
• Bit 1 = 1: Synchron with SM 2 event is
supported
• Bit 3:2 = 10: DC mode is supported
• Bit 5:4 = 01: Output shift with SYNC1 event
(only DC mode)
• Bit 14 = 1: dynamic times (measurement
through writing of 0x1C32:08)
UINT16
RO
0x8007
(32775
dec
)
0xC001
(EL3318)
1C32:05
Minimum cycle time
Minimum cycle time (in ns)
UINT32
RO
0x00000000
(0
dec
)
1C32:06
Calc and copy time
Minimum time between SYNC0 and SYNC1 event (in
ns, DC mode only)
UINT32
RO
0x00000000
(0
dec
)
1C32:08
Command
• 0: Measurement of the local cycle time is
stopped
• 1: Measurement of the local cycle time is
started
The entries 0x1C32:03, 0x1C32:05, 0x1C32:06,
0x1C32:09,
are updated with the maximum mea-
sured values.
For a subsequent measurement the measured values
are reset
UINT16
RW
0x0000 (0
dec
)
1C32:09
Delay time
Time between SYNC1 event and output of the outputs
(in ns, DC mode only)
UINT32
RO
0x00000000
(0
dec
)
1C32:0B
SM event missed
counter
Number of missed SM events in OPERATIONAL (DC
mode only)
UINT16
RO
0x0000 (0
dec
)
1C32:0C
Cycle exceeded
counter
Number of occasions the cycle time was exceeded in
OPERATIONAL (cycle was not completed in time or
the next cycle began too early)
UINT16
RO
0x0000 (0
dec
)
1C32:0D
Shift too short counter Number of occasions that the interval between SYNC0
and SYNC1 event was too short (DC mode only)
UINT16
RO
0x0000 (0
dec
)
1C32:20
Sync error
The synchronization was not correct in the last cycle
(outputs were output too late; DC mode only)
BOOLEAN
RO
0x00 (0
dec
)
Summary of Contents for EL33-00 Series
Page 2: ......
Page 6: ...Table of contents EL33xx 00x0 6 Version 4 2...
Page 17: ...Product overview EL33xx 00x0 17 Version 4 2 Fig 10 EL3312 Fig 11 EL3314...
Page 18: ...Product overview EL33xx 00x0 18 Version 4 2 Fig 12 EL3314 0002 Fig 13 EL3314 0010...
Page 61: ...Mounting and wiring EL33xx 00x0 61 Version 4 2 Fig 45 EL3314 0010 Fig 46 EL3314 0090...