Operational Commands:
RUN:
Parameters Passed: unit of speed, Speed, Direction.
Note:
Unit of Speed:
2
SPEED:
Ranges from 5 to 4780
RPM.(Rotary Mode) Ranges from 5 to
4780 RPM.(Linear Mode)
3
DIR :
DIR
VALUE
0x00
Clockwise
0x01
Counter clockwise
Example:
Command : 01,10,00,25,00,03,06,01,00,00,00,00,C8
01 -> Slave Address
10* -> Function Code
00* -> LSB Address of Holding Register
25* -> MSB Address of Holding Register
00, 03* -> Quantity of registers to be write in holding register
06* -> Total Byte count to be write in run command
01* -> Op-Code for RUN command
01 -> Counter clockwise direction
00 -> Speed is in RPM
00, 00, C8 -> total Speed value that is
200 rpm
(* indicates these values are fixed
)
Response: 01,10,00,25,00,03
Slave
Function
Holding
QTY of
Byte
Op-Code
Data
Address
Code
ADDR
Register
Count
1
10
0x25
3
6
1
DIR
Unit of
Speed
Speed
Unit of Speed
VALUE
0x00
RPM
0x01
RPH
0x02
MM_PER_SEC