21
ENFORCER Vandal Resistant Access Control Keypads
SECO-LARM U.S.A., Inc.
Programming the Output Mode and Output Timing:
The relays for outputs #1 and #2 can be programmed to trigger ON and OFF with a user code or
user card* (toggle mode), or to trigger for a programmed length of time of up to nearly 28 hours
before automatically turning OFF. The toggle or timed outputs can be used for locking or unlocking
a door or for a variety of functions that can be controlled with the keypad.
When programming the output mode and time, use this general formula:
aa bbbbb #
A
– Output
B
– Output Mode and Time
Outputs:
•
51
– Output #1
•
52
– Output #2
Output Mode and Time:
•
0
– Start/stop (toggle) mode. In this case, the output starts when a user code and/or user card*
is entered, and stops when a user code and/or card* is entered.
•
1
to
99999
– The output triggered by a user code and/or user card* lasts 1 to
99,999 seconds (nearly 28 hours) before automatically turning off (default 5 seconds).
NOTE
: While the keypad is in momentary timed output mode, the output can be reset any time
by entering the super user code.
Examples:
In these examples, assume that the super user code is
2580
.
1. In programming mode, set output #1 to toggle:
51 0 #
2.
In programming mode, set output #2 to 60 seconds:
52 60 #
3. Reset output #1 timer:
2580 # 1
4. Reset output #2 timer:
2580 # 2
*SK-1123-SPQ only