157
Display & Security
Parameter Name & Register Address
Integer Int +1
Float
Access
Values
& Description
LED 1 Label
Labels shown in display immediately below the 4 red LED
indicators. With up to 5 ASCII characters, which can read or
written using Modbus functions 16 or 23.
Valid characters are
0 to 9, a to z, A to Z, plus ß ö ( ) - and _.
Defaults: 1 = PRI (Primary); 2 = SEC (Secondary); 3 = TUNE (Tun-
ing); 4 = ALARM (Alarm)
Dec
7657
24040
48080
RW
Hex
1DE8
5DE8
BBDD
LED 1 Alternate Label
Dec
7660
24044
48088
RW
Hex
1DEC
5DEC
BBD8
LED 2 Label
Dec
7657
24041
48082
RW
Hex
1DE9
5DE9
BBD2
LED 2 Alternate Label
Dec
7661
24045
48090
RW
Hex
1DED
5DED
BBDA
LED 3 Label
Dec
7658
24042
48084
RW
Hex
1DEA
5DEA
BBD4
LED 3 Alternate Label
Dec
7662
24046
48092
RW
Hex
1DEE
5DEE
BBDC
LED 4 Label
Dec
7659
24043
48086
RW
Hex
1DEB
5DEB
BBD6
LED 4 Alternate Label
Dec
7663
24047
48094
RW
Hex
1DEF
5DEF
BBDE
LED 1 Useage
Value
LED 1 Usage. For 8 & 9 see also LED 1 Selections
Dec
7868
24252
48504
RW
0
Loop 1 Primary Control ON = LED 1 ON
Hex
1EBC
5EBC
BD78
1
Loop 1 Secondary Control ON = LED 1 ON
2
Loop 2 Primary Control ON = LED 1 ON
3
Loop 2 Secondary Control ON = LED 1 ON
4
Loop 1 VMD Open ON = LED 1 ON
5
Loop 1 VMD Close ON = LED 1 ON
6
Loop 2 VMD Open ON = LED 1 ON
7
Loop 2 VMD Close ON = LED 1 ON
8
Alarm/Event/Digital/Control (Logical
OR)
9
Alarm/Event/Digital/Control inverted (Logical
NOR)
Value 8 (Logical
OR selection of Alarm/Events/Digital/Control) turns ON the LED if any of the selected alarms,
events, inputs or functions are active.
Value 9 (Logical
NOR selection of Alarm/Events/Digital/Control) turns OFF the LED if any of the selected alarms,
events, inputs or functions are active.
Note: Pre-tune will flash the LED instead of turning it on, but flashing will be obscured if used in conjunc-
tion with other functions when they are on.
Summary of Contents for Chromalox 4081
Page 2: ...B ...