Returns the number of unused segments remaining in the instrument. The number will be between 0 and 255,
depending on how many have been used in the profiles so far created.
Read A Profile Header - Request (to instrument)
Field Name
Data
Comments
Dec
Hex
Unit Address
A/R
A/R
The network address ID of the instrument.
Function Code
23
17
Requires the multi read/write function.
Read Start Address High Byte
32
20
Read Start Address Low Byte
6
6
Read Quantity Of Registers High Byte
0
0
Read Quantity Of Registers Low Byte
19
13
Write Start Address High Byte
32
20
Write Start Address Low Byte
6
6
Write Quantity Of Registers High Byte
0
0
Write Quantity Of Registers Low Byte
2
2
Byte Count
4
4
Command Code High Byte
82
52
Profile Number from 0 to 63
Command Code Low Byte
80
50
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
The instrument replies to this message with an Edit Response Message.