59
Expert Power Control 8221/8226
© 2021 GUDE Systems GmbH
Specifications
epc8226OVPStatus
.58.1.5.2.1.2.x
INTEGER
RO
shows the status of the built-in Overvoltage Protection
epc8226spActivePowerChan
.58.1.5.5.1.0
Unsigned32
RO
Number of Single Port Power Channels. Value is zero on EPC 8220
series.
epc8226spPowerIndex
.58.1.5.5.2.1.1.x
Integer32
RO
Index of Single Port Power Channel entries. Indices 0-5 mean Ports A1
to A6, 6-11 are Ports B1 to B6.
epc8226spChanStatus
.58.1.5.5.2.1.2.x
Integer32
RO
0 = data not active, 1 = data valid
epc8226spAbsEnergyActive
.58.1.5.5.2.1.3.x
Gauge32
RO
Absolute Active Energy counter.
epc8226spPowerActive
.58.1.5.5.2.1.4.x
Integer32
RO
Active Power
epc8226spCurrent
.58.1.5.5.2.1.5.x
Gauge32
RO
Actual Curent on Power Channel.
epc8226spVoltage
.58.1.5.5.2.1.6.x
Gauge32
RO
Actual Voltage on Power Channel
epc8226spFrequency
.58.1.5.5.2.1.7.x
Gauge32
RO
Frequency of Power Channel
epc8226spPowerFactor
.58.1.5.5.2.1.8.x
Integer32
RO
Power Factor of Channel between -1.0 and 1.00
epc8226spPangle
.58.1.5.5.2.1.9.x
Integer32
RO
Phase Angle between Voltage and L Line Current between -180.0 and
180.0
epc8226spPowerApparent
.58.1.5.5.2.1.10.x
Integer32
RO
L Line Mean Apparent Power
epc8226spPowerReactive
.58.1.5.5.2.1.11.x
Integer32
RO
L Line Mean Reactive Power
epc8226spAbsEnergyReactive
.58.1.5.5.2.1.12.x
Gauge32
RO
Absolute Reactive Energy counter.
epc8226spAbsEnergyActiveReset-
table
.58.1.5.5.2.1.13.x
Gauge32
RW
Resettable Absolute Active Energy counter. Writing '0' resets all reset-
table counter.
epc8226spAbsEnergyReactiveRe-
settable
.58.1.5.5.2.1.14.x
Gauge32
RO
Resettable Absolute Reactive Energy counter.
epc8226spResetTime
.58.1.5.5.2.1.15.x
Gauge32
RO
Time in seconds since last Energy Counter reset.
epc8226spForwEnergyActive
.58.1.5.5.2.1.16.x
Gauge32
RO
Forward Active Energy counter.
epc8226spForwEnergyReactive
.58.1.5.5.2.1.17.x
Gauge32
RO
Forward Reactive Energy counter.
epc8226spForwEnergyActiveRe-
settable
.58.1.5.5.2.1.18.x
Gauge32
RO
Resettable Forward Active Energy counter.
epc8226spForwEnergyReact-
iveResettable
.58.1.5.5.2.1.19.x
Gauge32
RO
Resettable Forward Reactive Energy counter.
epc8226spRevEnergyActive
.58.1.5.5.2.1.20.x
Gauge32
RO
Reverse Active Energy counter.
epc8226spRevEnergyReactive
.58.1.5.5.2.1.21.x
Gauge32
RO
Reverse Reactive Energy counter.
epc8226spRevEnergyActiveReset-
table
.58.1.5.5.2.1.22.x
Gauge32
RO
Resettable Reverse Active Energy counter.
epc8226spRevEnergyReactiveRe-
settable
.58.1.5.5.2.1.23.x
Gauge32
RO
Resettable Reverse Reactive Energy counter.
epc8226PwrSupplyIndex
.58.1.5.13.1.1.x
Integer32
RO
Index of Power Supply entries
epc8226PwrSupplyStatus
.58.1.5.13.1.2.x
INTEGER
RO
shows status of the Power Supply for each bank
epc8226NTPTimeValid
.58.1.5.15.1.0
INTEGER
RO
Show if valid Time is received
epc8226NTPUnixTime
.58.1.5.15.2.0
Unsigned32
RO
show received NTP time as unixtime (secs since 1 January 1970)
epc8226NTPLastValidTimestamp
.58.1.5.15.3.0
Unsigned32
RO
show seconds since last valid NTP timestamp received
epc8226SensorIndex
.58.1.6.1.1.1.x
Integer32
RO
None
epc8226TempSensor
.58.1.6.1.1.2.x
Integer32
RO
actual temperature
epc8226HygroSensor
.58.1.6.1.1.3.x
Integer32
RO
actual humidity
epc8226InputSensor
.58.1.6.1.1.4.x
INTEGER
RO
Summary of Contents for Expert Power Control 8221 Series
Page 2: ...2 Expert Power Control 8221 8226 2021 GUDE Systems GmbH ...
Page 5: ...Device Description ...
Page 13: ...13 Expert Power Control 8221 8226 2021 GUDE Systems GmbH Device Description ...
Page 14: ...Operating ...
Page 24: ...Configuration ...
Page 50: ...Specifications ...
Page 91: ...Support ...