APPENDIX PARAMETER OBJECT LISTS
30
Function
Inst
Attr
Size
Monitoring/Setting Range
Magnifi-
cation
Access
rule
Com
mand
ZERO Speed Level (Param261)
1
163
2
0.00 to 100.00(Hz)
100
Get/Set
C063
Data Command Sel (Param262)
1
170
1
02(Operator)/03(RS485)/
04(Option 1)/05(Option 2)
1
Get/Set
C070
CommSpeed Select (Param263)
1
171
1
02(loop back)/
03(2400bps)/04(4800bps)/
05(9600bps)/06(19200bps)
1
Get/Set
C071
Comm ID Select (Param264)
1
172
1
1 to 32
1
Get/Set
C072
CommBitLengthSel (Param265)
1
173
1
7(7bit)/8(8bit)
1
Get/Set
C073
CommParitySelect (Param266)
1
174
1
00(No Parity)/01( Even Parity)/
02(Odd Parity)
1
Get/Set
C074
Comm StopBit Sel (Param267)
1
175
1
1(1bit)/2(2bit)
1
Get/Set
C075
Comm Wait Time (Param268)
1
178
2
0 to 1000(ms)
1
Get/Set
C078
O Adjustment (Param269)
1
181
2
0 to 65530
1
Get/Set
C081
OI Adjustment (Param270)
1
182
2
0 to 65530
1
Get/Set
C082
O2 Adjustment (Param271)
1
183
2
0 to 65530
1
Get/Set
C083
Therm-Adjustment (Param272)
1
185
2
0.0 to 1000.0
10
Get/Set
C085
AM Offset Adjust (Param273)
1
186
1
0.0 to 10.0(V)
10
Get/Set
C086
AMI Adjustment (Param274)
1
187
1
0 to 255(%)
1
Get/Set
C087
AMI OffsetAdjust (Param275)
1
188
1
0.0 to 20.0( mA)
10
Get/Set
C088
Support service
Service name
Code
Get_Attribute_Single
H’0E
Set_Attribute_Single
H’10
(6) Extend Group C object Class ID=106
Function
Inst
Attr
Size
Monitoring/Setting Range
Magnifi-
cation
Access
rule
Com-
mand
UP/DWN Selection (Param276)
1
101
1
00(Not keep)/01(Keep)
1
Get/Set
C101
Reset Selection (Param277)
1
102
1
00(Reset at close)/
01(Reset at open)/
02(Only trip clear)
1
Get/Set
C102
Reset f MacthSel (Param278)
1
103
1
00(0Hz start)/01(Synchronize)
1
Get/Set
C103
OL Alarm Level 2 (Param279)
1
111
2
0 to 200(%) (constant current)
1
Get/Set
C111
O ZeroAdjustment (Param280)
1
121
2
0 to 65530
1
Get/Set
C121
OIZeroAdjustment (Param281)
1
122
2
0 to 65530
1
Get/Set
C122
O2ZeroAdjustment (Param282)
1
123
2
0 to 65530
1
Get/Set
C123
Support service
Service name
Code
Get_Attribute_Single
H’0E
Set_Attribute_Single
H’10
(7) Extend Group H object Class ID=107
Function
Inst
Attr
Size
Monitoring/Setting Range
Magnifi-
cation
Access
rule
Com
mand
AutotuningSelect (Param283)
1
101
1
00(Invalid)/01(Valid(not rotate))/
02(Valid(rotate))
1
Get/Set
H001
Motor Constant (Param284)
1
102
1
00(Standard Motor)/
01(Offline Auto)/02(Online Auto)
1
Get/Set
H002
2nd Motor Constant (Param351)
2
102
1
00(Standard Motor)/
01(Offline Auto)/02(Online Auto)
1
Get/Set
H202
Allowable Motor (Param285)
1
103
1
00(0.20)/01(0.37)/02(0.40)/
03(0.55)/04(0.75)/05(1.10)/
06(1.50)/07(2.20)/08(3.00)/
09(3.70)/10(4.00)/11(5.50)/
12(7.50)/13(11.0)/14(15.0)/
15(18.5)/16(22.0)/17(30.0)/
18(37.0)/19(45.0)/20(55.0)/
21(75.0)
1
Get/Set
H003
2nd Allowable Motor (Param352)
2
103
1
Same above
1
Get/Set
H203
MotorPole Select (Param286)
1
104
1
0(2P)/1(4P)/2(6P)/3(8P)
1
Get/Set
H004
2nd MotorPole Select(Param353)
2
104
1
0(2P)/1(4P)/2(6P)/3(8P)
1
Get/Set
H204
Speed Response (Param287)
1
105
2
0.001 to 65.53
1000
Get/Set
H005
2nd Speed Response(Param354)
2
105
2
0.001 to 65.53
1000
Get/Set
H205
StabilizedFactor (Param288)
1
106
2
0 to 255
1
Get/Set
H006
2nd StabilizedFactor (Param355)
2
106
2
0 to 255
1
Get/Set
H206