iEM-RS Series Modbus RS485 Integrated Stepper Motor
17
Note: (1) If the input or output function is set repeatedly, only after the restart drive can detect it.
(2) When input functions are configured, it is effective after clicking save and restart drive.
Digital Input port function assignment:
Normal-open (N.O); Normal-closed (N.C).
Digital Inputs
Digital Outputs
Functions
Symbols
Type
Functions
Symbols
Type
N.O.
N.C.
N.O.
N.C.
Trigger Command
CTRG
0x20
0xA0
Command Complete
CMD_OK
0x20
0xA0
Homing Trigger
HOME
0x21
0xA1
Path Complete
MC_OK
0x21
0xA1
Quick Stop
STP
0x22
0xA2
Homing Complete
HOME_OK
0x22
0xA2
JOG+
JOG+
0x23
0xA3
Alarm
ALM
0x25
0xA5
JOG-
JOG-
0x24
0xA4
Brake
BRK
0x24
0xA4
Positive Limit
PL
0x25
0xA5
In-position
PEND
0x23
0xA3
Negative Limit
NL
0x26
0xA6
-
Home switch
ORG
0x27
0xA7
Path Address 0
ADD0
0x28
0xA8
Path Address 1
ADD1
0x29
0xA9
Path Address 2
ADD2
0x2A
0xAA
Path Address 3
ADD3
0x2B
0xAB
Clear Error
CLR
0x07
0x87
Enable
SRV-ON
0x08
0x88
4.3.3 Smooth Filter Time Setting for Digital Inputs
This section describes the setting of the value of each bit of the registers of the 7 inputs, where the filtering time is set by the
high 8 bits.
Set value of low 8 bits:
Normally open. Normally closed setting
Digital input function setting
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
0: Normally open
1: Normally closed
(000 0000) 0x00: Invalid input.
(000 1000) 0x08: Enable.
(010 0000)0x20: CTRG.
(010 0001)0x21: Homing trigger.
(010 0010) 0x22: Quick stop.
(010 0011) 0x23: JOG+.
(010 0100) 0x24: JOG-.
(010 0101) 0x25: Positive limit.
(010 0110) 0x26: Negative limit.
(010 0111) 0x27: Home switch.
(010 1000) 0x28: Path address 0.
(010 1001) 0x29: Path address 1.
(010 1010) 0x2A: Path address 2.
(010 1011) 0x2B: Path address 3.
(010 1100)0x2C: JOG2 velocity