e. If next segment’s “OUT” set to “0”, the program will end at this segment. If the program needs repeat, it has to
enter level 4 and set “PROG. 4th digit” to “1”.
f . Function key for program:
In the intial window status, pushing ”up” key
for 4 sec., the program start and “pro” LED flickers, pushing
“down” key
for 4 sec., the program pause and “PRO” LED keeps light.
If pushing “UP” key first then pushing key again, the program will jump to next segment, but if pushing
“down” key first then pushing key again, the program will end immediately and “PRO” LED is “off”.
g. Alarm function for program:
1).Segment ending alarm
“AL1/AL2/AL3” & “ALD1/ALD2/ALD3” in level 3 must be set.
example: Set “ALD1” to “07”
Set “AL1” to “2”, the alarm function will perform in segment 2
Set “ALT1” to “00.20 M/S.” the alarm will perform 20 sec., 00.20 H/M. the alarm will perform 20 MIN If set
it to “0” the alarm is in flicker but if set it to “99.59” the alarm is in continuance.
2).Program ending alarm:
“ALD1/ALD2/ALD3” in level 3 must be set.
example: Set “ALD2” to “17”, if the “PROG. 1
st
digit in level 4” set “1”, the alarm2 will perform when the program
end, but if the “PROG. 1
st
digit” set “0”, the alarm2 will perform during program process then it stops
when the program end.
h. Other functions:
1).Power failure function:
If the “PROG. 1
st
digit” set “1”, it has power failure function the program will perform again from stopped
segment when the power is recovered. On the contrary, if the “PROG. 1
st
digit ” set “0”, it hasn’t power failure
function, the program always perform again from first segment when the power is recovered.
2).When the program start from first segment, if “the PROG. 2
nd
digit” set “1”, it will start according to “PV” but if
the “PROG. 2
nd
digit” set “0”, it will start according to “0”, if it is set to start from PV, the controller will check PV
& SV-1 which is small if PV is small it will start from PV but if SV-1 is small it will start from SV-1.
3).Wait function:
If the “WAIT” parameter in level3 set “0”, it has not wait function, but if it sets other volume the SV will wait the
PV when the PV exceed the SV over the set volume.
4.Remote SV function:
a. It needs modifying hardware (contact the distributor)
b. Set the “MODE. 1
st
digit” to “1” and the “MODE. 4
th
& 3
rd
digit” to “11” in level 4.
5.Master and slaver function:
a. Both master and slaver need installing TTL communication hardware.
b. The master unit must be with program function, then setting its “TIM2. 4
th
& 3
rd
” to “11” and “FUNC. 1
st
digit” to “1” in level4. in addition to set “IDNO” parameter to “0” and “BAUD” parameter with ideal volume in level3.
c. The slaver unit must be without program function, then setting “TIM2. 4
th
& 3
rd
digit” to “11”, “FUNC. 2
nd
digit” to
“1” “MODE. 4
th
& 3
rd
digit” to “11” and “MODE. 1
st
digit” to “0” in level4 in addition to set among
“ALD1/ALD2/ALD3” to “0” in level3. In this case one among “AL1/AL2/AL3” will convert to “RATE” function.
SET
SET
P.8