ioPAC 8020 Rugged Remote I/O
Modbus/TCP Address Mappings
C-4
0x001C
R/W
10 Word
IP filter enable list
0x0026
R/W
20 Word
IP filter IP list
0x003A
R/W
20 Word
IP filter mask list
0x004E
R/W
20 Word
Time server
0x0062
R/W
20 Word
Log server
0x0076
R/W
1 Word
Log server port number
0x0077
R/W
30 Word
Location
0x0096
W
1 Word
Memorize the module configuration
0: clear module combination
1: commit current module
combination
0x00B3
R/W
1 Word
Memorize the module configuration
0: clear module combination
1: commit current module
combination
0x00B4
R/W
1 Word
Hot-swap safe mode discard
1: NOT go to safe mode if module
change
0: go to safe mode if module change
0x00B5
R/W
1 Word
SNMP enable/disable
1: Enable
0: Disable
0x00B6
R/W
1 Word
SNMP version
Bit0:V1, bit 1:V2, Bit2: V3
0x2000
R/W
1
Click&Go start/stop
1: Start
0: Stop
5xxxx Write Registers (Support function 8)
Sub-function
(Request)
(Response)
Description
0x0001
0xFF00
Echo Request Data
Reboot
0x0001
0x55AA
Echo Request Data
Reset with Factory default
Module Configuration Map
For 16Channel Digital Output Module (RM-2600-T):
Address offset
Access
Data Format
Description
0x0000
Read-only
1 Word
Module ID
0x0001
Read-only
1 Word
HW version
0x0002
Read-only
1 Word
FW version
0x0003
Read-only
1 Word
Series number
0x0004
Read-only
1 Word
Number of channels
0x0005
Read-only
1 Word
Channel Occupied by Logic
Holding register map(R/W)
Address offset
Access
Data Format
Description
0x0000~8N-1
R/W
1 Word
Channel alias name
8N~16N-1
R/W
1 Word
Alias for ON status
16N~24N-1
R/W
1 Word
Alias for OFF status
Coil map(R/W)
Address offset
Access
Data Format
Description