14 Serial Communications
14-12
CP2E CPU Unit Software User’s Manual(W614)
Built-in RS-2
3
2C, Built-in RS-4
8
5 or Serial Port Tab Page
Parameter
Setting
Communications
Settings
Set the communications settings to the same values as the connected device.
If the connected device is set to 9,600 bps, two stop bits, and even parity, select the
Cu
s
tom
Option, set the baud rate to 9,600 and format to
7,2,E
.
Mode
Select
RS-2
3
2C
.
End Code
•
To specify the number of bytes of received data, select Received
byte
s
and set the
number of bytes from 1 to 256.
•
To use CR+LF as the end code, set CR+LF.
•
To set the end code to any value between 00 to FF hex, set a value between
0x0000 and 0x00FF.
14-3-4 Related Auxiliary Area Bits and Words
Address
Name
Details
A
3
92.04
Serial Port 1/Built-in RS-2
3
2C
Port Communications Error
Flag
ON when a communications error occurs at the serial port 1 or built-in
RS-2
3
2C port. The port must be restarted when this flag turns ON.
A
3
92.05
Serial Port 1/Built-in RS-2
3
2C
Port Send Ready Flag
(No-protocol mode)
ON when the serial port 1 or built-in RS-2
3
2C port is able to send data
in no-protocol mode.
A
3
92.06
Serial Port 1/Built-in RS-2
3
2C
Port Reception Completed
Flag
(No-protocol mode)
ON when the serial port 1 or built-in RS-2
3
2C port has completed the
reception in no-protocol mode.
•
When the number of bytes was specified: ON when the specified
number of bytes is received.
•
When the end code was specified: ON when the end code is received
or 256 bytes are received.
A
3
92.07
Serial Port 1/Built-in RS-2
3
2C
Port Reception Overflow Flag
(No-protocol mode)
ON when a data overflow occurred during reception through the serial
port 1 or built-in RS-2
3
2C port in no-protocol mode.
•
When the number of bytes was specified:
ON when more data is received after the reception was completed but
before RXD was executed.
•
When the end code was specified:
ON when more data is received after the end code was received but
before RXD is executed.
ON when 257 bytes are received before the end code.
If a start code is specified, ON when the end code is received after
the start code is received.
A
3
92.12
Serial Port 2/Built-in RS-4
8
5
Port Communications Error
Flag
ON when a communications error has occurred at the serial port 2 or
built-in RS-4
8
5 port. The port must be restarted when this flag turns
ON.
A
3
92.1
3
Serial Port 2/Built-in RS-4
8
5
Port Send Ready Flag
(No-protocol Mode)
ON when the serial port 2 or built-in RS-4
8
5 port is able to send data in
no-protocol mode.
A
3
92.14
Serial Port 2/Built-in RS-4
8
5
Port Reception Completed
Flag
(No-protocol Mode)
ON when the serial port 2 or built-in RS-4
8
5 port has completed the
reception in no-protocol mode.
•
When the number of bytes was specified: ON when the specified
number of bytes is received.
•
When the end code was specified: ON when the end code is received
or 256 bytes are received.
Summary of Contents for SYSMAC CP Series
Page 3: ......
Page 32: ...1 Overview 1 4 CP2E CPU Unit Software User s Manual W614 ...
Page 44: ...3 CPU Unit Operation 3 8 CP2E CPU Unit Software User s Manual W614 ...
Page 116: ...6 I O Allocation 6 8 CP2E CPU Unit Software User s Manual W614 ...
Page 144: ...7 PLC Setup 7 28 CP2E CPU Unit Software User s Manual W614 ...
Page 170: ...10 Interrupts 10 14 CP2E CPU Unit Software User s Manual W614 ...
Page 200: ...11 High speed Counters 11 30 CP2E CPU Unit Software User s Manual W614 ...
Page 272: ...12 Pulse Outputs 12 72 CP2E CPU Unit Software User s Manual W614 ...
Page 278: ...13 PWM Outputs 13 6 CP2E CPU Unit Software User s Manual W614 ...
Page 460: ...18 Programming Device Operations 18 28 CP2E CPU Unit Software User s Manual W614 ...
Page 576: ...Revision 2 CP2E CPU Unit Software User s Manual W614 ...
Page 577: ......