A-91
Appendices
CP2E CPU Unit Software User’s Manual(W614)
A-2 A
u
xil
iar
y Area A
llocation
s b
y
Ad
dress
App
A-2-2 Read/Wr
ite W
ords
A571
0
8
UDP Open Request
Switch for Socket
No.2
When the flag changes from OFF to
ON, UDP open processing is
executed.
When open process is completed, the
flag automatically turns OFF.
OFF to ON: UDP
open
---
Cleared
---
09
TCP Passive Open
Request Switch for
Socket No.2
When the flag changes from OFF to
ON, TCP passive open processing is
executed.
When open process is completed, the
flag automatically turns OFF.
OFF to ON: TCP
passive open
---
Cleared
---
10
TCP Active Open
Request Switch for
Socket No.2
When the flag changes from OFF to
ON, TCP active open processing is
executed.
When open process is completed, the
flag automatically turns OFF.
OFF to ON: TCP
active open
---
Cleared
---
11
Send Request Switch
for Socket No.2
When the flag changes from OFF to
ON, transmission processing is
executed.
When transmission process is
completed, the flag automatically turns
OFF.
OFF to ON: Send
---
Cleared
---
12
Receive Request
Switch for Socket
No.2
When the flag changes from OFF to
ON, reception processing is executed.
When reception process is completed,
the flag automatically turns OFF.
OFF to ON: Receive
---
Cleared
---
1
3
Close Request Switch
for Socket No.2
When the flag changes from OFF to
ON, close processing is executed.
When close process is completed, the
flag automatically turns OFF.
OFF to ON: Close
---
Cleared
---
A572
00
UDP Open Request
Switch for Socket
No.
3
When the flag changes from OFF to
ON, UDP open processing is
executed.
When open process is completed, the
flag automatically turns OFF.
OFF to ON: UDP
open
---
Cleared
---
01
TCP Passive Open
Request Switch for
Socket No.
3
When the flag changes from OFF to
ON, TCP passive open processing is
executed.
When open process is completed, the
flag automatically turns OFF.
OFF to ON: TCP
passive open
---
Cleared
---
02
TCP Active Open
Request Switch for
Socket No.
3
When the flag changes from OFF to
ON, TCP active open processing is
executed.
When open process is completed, the
flag automatically turns OFF.
OFF to ON: TCP
active open
---
Cleared
---
0
3
Send Request Switch
for Socket No.
3
When the flag changes from OFF to
ON, transmission processing is
executed.
When transmission process is
completed, the flag automatically turns
OFF.
OFF to ON: Send
---
Cleared
---
04
Receive Request
Switch for Socket
No.
3
When the flag changes from OFF to
ON, reception processing is executed.
When reception process is completed,
the flag automatically turns OFF.
OFF to ON: Receive
---
Cleared
---
05
Close Request Switch
for Socket No.
3
When the flag changes from OFF to
ON, close processing is executed.
When close process is completed, the
flag automatically turns OFF.
OFF to ON: Close
---
Cleared
---
A5
8
0
00
to
0
3
FB Communications
Instruction Retries
Count
Automatically stores the number of
retries of FB communication
instruction settings in the PLC Setup.
0 to F hex
Set the
PLC
Settings
Cleared
Written at the
start of
operation.
A5
8
1
---
FB Communications
Instruction Response
Monitoring Time
Automatically stores the FB
communication instruction response
monitoring time settings in the PLC
Setup.
0001 to FFFF hex
(unit 0.1 s: 0.1 to
655
3
.5 s)
0000 Hex: 2 s
Set the
PLC
Settings
Cleared
Written at the
start of
operation.
Address
Name
Function
Settings
Status
after
mode
change
Status at
startup
Write
timing
Related
flags,
settings
Words
Bits
Summary of Contents for SYSMAC CP Series
Page 3: ......
Page 32: ...1 Overview 1 4 CP2E CPU Unit Software User s Manual W614 ...
Page 44: ...3 CPU Unit Operation 3 8 CP2E CPU Unit Software User s Manual W614 ...
Page 116: ...6 I O Allocation 6 8 CP2E CPU Unit Software User s Manual W614 ...
Page 144: ...7 PLC Setup 7 28 CP2E CPU Unit Software User s Manual W614 ...
Page 170: ...10 Interrupts 10 14 CP2E CPU Unit Software User s Manual W614 ...
Page 200: ...11 High speed Counters 11 30 CP2E CPU Unit Software User s Manual W614 ...
Page 272: ...12 Pulse Outputs 12 72 CP2E CPU Unit Software User s Manual W614 ...
Page 278: ...13 PWM Outputs 13 6 CP2E CPU Unit Software User s Manual W614 ...
Page 460: ...18 Programming Device Operations 18 28 CP2E CPU Unit Software User s Manual W614 ...
Page 576: ...Revision 2 CP2E CPU Unit Software User s Manual W614 ...
Page 577: ......