8.6 Data sets
3WL/3VL circuit breakers with communication capability - PROFIBUS
222
System Manual, 03/2011, A5E01051353-02
8.6.13
Data set DS 91 statistical information
The table below shows the content of data set 91 in which the statistical information on the
SENTRON circuit breakers is transmitted. As with the other data sets, the property of each
data point is additionally transmitted in the property byte.
The table below contains the data sets DS91: Statistical information (length 84 bytes, read-
only):
Table 8- 26 Content of data set 91
Byte
Description
Data
point
Source
WL
Source
VL
Format
Length
(bits)
Scaling
0
Number of switching operations under load
80
COM15
COM20
unsigned
int
16
0
2
Number of switching operations caused by
trips
81
COM15
COM20
unsigned
int
16
0
4
Switching cycle counter
(for switching cycle on/off)
82
COM15
—
unsigned
int
16
0
6
Runtime meter
(when On + current > 0)
83
COM15
COM20
unsigned
long
32
0
10
Date of the last parameter change
84
COM15
—
Time
64
—
18
Number of short-circuit releases (SI)
104
ETU
COM20
unsigned
int
16
0
20
Number of overload trips (L)
105
ETU
COM20
unsigned
int
16
0
22
Number of ground-fault tripping operations
(G)
106
ETU
COM20
unsigned
int
16
0
24
Total of deactivated I²t values L1, L2, L3, N
107
ETU
—
Format
(107)
128
0
40
Maintenance information about the main
contacts
405
ETU
—
Format
(405)
2
—
41
Reserved
—
—
—
—
56
—
48
Modules connected to c
88
COM15
—
Format
(88)
32
—
52
Reserved
—
—
—
—
144
—
70
Property byte for byte 0 (number of switching
operations under load)
—
COM15
COM20
PB
8
—
71
Property byte for byte 2 (number of switching
operations caused by trips)
—
COM15
COM20
PB
8
—
72
Property byte for byte 4 (switching cycle
counter (for switching cycle on/off))
—
COM15
—
PB
8
—
73
Property byte for byte 6 (runtime meter
(when On + current > 0))
—
COM15
COM20
PB
8
—
74
Property byte for byte 10 (date of last
parameter change)
—
COM15
—
PB
8
—
75
Property byte for byte 18 (number of short-
circuit tripping operations (SI))
—
ETU
COM20
PB
8
—
76
Property byte for byte 20 (number of overload
trips (L))
—
ETU
COM20
PB
8
—