POSIDRIVE
®
FDS 4000
STÖBER
ANTRIEBSTECHNIK
10. Positioning Control
14
10.4
Absolute / relative positioning
One of 4 possible traversing methods (parameters
J11
,
J21
,
J31
and so on) can be assigned to each process block.
•
Relative
•
Absolute
•
Continuous, positive
•
Continuous, negative
A
relative
path always refers to the current location (chain
dimensions).
An
absolute
position refers to a fixed reference point (i.e.,
machine zero point) which is determined with
reference
traversing
. See chapter 10.6. For this reason, an absolute
position always requires reference traversing. Any start
commands given without reference traversing are answered
by the inverter with "
51:refused
".
When a process block is defined as
continuous
and a start
command is given, the axis continues to move in the specified
direction until a signal arrives from the outside (e.g.,
posi.next
or
posi.start
). The speed can be adjusted via an analog input
(e.g., set the AE2 function
F20
=
5:Override
for this.)
Successful conclusion of a movement is signaled via the out-
put signal
reference value-reached
(
F00
=3 and
F80
=3). This
signal appears when the actual position lands in the
position
window
(destination ±
I22
) for the first time. The signal is not
withdrawn until the next traversing command is given.
10.5
Commissioning
This section only covers the drive with encoder feedback
(
B20
=2).
Important
: Before positioning control is activated, speed
control must be commissioned (chapter 9.6) and, if necessary,
optimized with FDS Scope.
Positioning control is activated with
C60
=
2:Position
The
status indicator
changes and displays the actual position
in the first line.
If
B20
≠
2, the first line continues to show speed and current.
While process blocks are being processed, the lower line also
indicates the number of the active process block.
Important:
If you want to change the location of the decimal
point in the position display via
I06
(
I06
=decimal point shift),
do this at the beginning of commissioning since the
significance of all positions is changed.
10.5.1
Limited traversing range
Limited position range (I00=0)
M
Limited traversing range means that the permissible area of
movement is restricted by end stops or similar. Safety requires
that
limit switches
be provided. If the inverter is not equipped
with a sufficient number of free inputs (i.e., operation without
an option board), the limit switches must be evaluated by a
higher level controller. The primary parameters are listed
below:
•
I00
=0 Limited traversing range
•
I05:
Unit of measurement
(e.g., mm, degree (°) and inch,
user
•
I06:
Number of decimal places
•
I07:
Distance per encoder revolution
(e.g., mm/U)
•
I10:
Maximum speed (e.g., mm/sec)
•
I11:
Maximum acceleration (e.g., mm/sec
2
)
•
I12:
Tip mode speed
Important:
Since some parameters in groups
I
and
J
(e.g.,
paths or accelerations) may assume very large values, the
keys can be used to directly select the tens exponent to be
changed. Only the individual digit flashes and not the entire
number. The
keys can be used to increment/decrement
the value by the selected tens exponent:
Ö
Before starting testing, check the limit switches, and
decouple the drive from the machine if necessary.
The enable can now be activated as the first test. The display
indicates
17: posi.active .
The position control loop functions, and the current position is
maintained. During the next step, the drive is moved via
tip
mode (i.e., inching mode)
. Set parameter
J03
=1 for this. The
keys can be used to traverse the drive.
Ö
The speed can also be changed during traversing via
analog input AE2 (
F20
=5).
The next step is the commissioning of reference traversing.
See chap. 10.6.
Software limit switches
I50
and
I51
can be
programmed with a reference axis (
I86
=1). The software limit
switches prevent movement to positions outside
I50
and
I51
.
A short relative movement (
J11
=0) can be specified for testing
purposes in
J10
(destination position process block 1). The
speed is entered in
J12
, while the ramps are entered in
J13
and
J14
.
J00
=1 can be used to start and monitor the
movement. Do not forget the enable.
ready
Act. position
Oper. status
(See chap. 16)
Brake chopper active
Single digit flashing
Changes with
Digit selection with
position
Position
Oper. status
(See chap. 16)
Process block no.
travers