Parameter lock.
This security feature locks out selected levels or single
parameters prohibiting tampering and inadvertent programming changes.
0000
All parameters are locked.
0001
Only SP is adjustable.
0010
USER (level) and A1(parameter) are adjustable.
0011
USER
、
PID(level) and A1
、
A2(parameter) are adjustable.
0100
USER
、
PID
、
OPTI(level) and A1
、
A2(parameter) are adjustable.
1000
Additional A3(parameter). All parameter you can find out,but
can’t adjustable.
1001
Additional A3(parameter)
,
only SP is adjustable.
1010
Additional A3(parameter). USER(level) and A1(parameter) are
adjustable.
1011
USER
、
PID (level) and A1
、
A2
、
A3 (parameter) are adjustable.
1100
All parameters in all level are opened.
THIRD PROGRAMMING LEVEL PARAMETERS
CODE
DESCRIPTION RANGE
Default
Input type selection.
TYPE
RANGE(
℃
) RANGE(
℉
)
J
-50
〜
1000
-58
〜
1832
K
-50
〜
1370
-58
〜
2498
T
-270
〜
400
-454
〜
752
E
-50
〜
1000
-58
〜
1832
B
0
〜
1800
32
〜
3272
R
-50
〜
1750
-58
〜
3182
S
-50
〜
1750
-58
〜
3182
N
-50
〜
1300
-58
〜
2372
C
-50
〜
1800
-58
〜
3272
D-PT
-200
〜
850
-328
〜
1652
J-PT
-200
〜
600
-328
〜
1112
LINE
-1999
〜
9999
Refer to figure.
K
Unit of process value.
The parameter is not displayed when
=LinE
:
Degrees C.
:
Degrees F.
℃
Used to limit the process value when linear input
(type=line) signal is out of range.
None=
this function is not used.
Lo =
The process value will be limited to LoLt when input
signal is lower than the scale range.
Hi =
The process value will be limited to HiLt when input
signal is higher than the scale range.
Lo.Hi =
The process value will be limit within the range of
LoLt to HiLt when input signal is out of scale.
nonE
,
Lo
Hi
,
Hi.Lo
Decimal Point selection.
0000
:
No decimal point.
000.0
:
0.1 resolution
00.00
:
0.01 resolution, used for linear input only.
0.000
:
0.001 resolution, used for linear input only.
After changing the decimal point parameter please re-check
all the parameters.
0000
000.0
00.00
0.000
0000
Output control action.
:Reverse
action
for heating.
:Direct action for
cooling.
8