31
Integration into existing systems
The outputs must be set in
Output Mode
Menu.
Actions with text messages
For the actions that allow the sending of alarm, message and other texts, placehol-
ders can be used within the text that are replaced with actual contents, such as IO
states, time, etc., when an action is executed.
Placeholder
Description
<ox>
State of the outputs No. x (ON/OFF)
<cx>
Counter state No. x
<o>
State of all outputs as hex. bit pattern
<dn>
Device Name
<onx>
Name of the output No. x
<t>
Time stamp with date and time
<$y>
Year in format „YYYY“
<$m>
Month in format „MM“
<$d>
Day in format „DD“
<$h>
Hour in format „hh“
<$i>
Minutes in format “mm“
<$s>
Seconds in format „ss“
In addition to the actual message that is sent when the action is triggered, a clear
message can also be stored in the text messages. The clear message is sent when
the trigger for the action is no longer present - i.e. the normal state returns. Sending
messages takes different amounts of time depending on the protocol. If the trig-
gering state is only present for such a short time that the corresponding message
could not yet be sent, only the Clear message is sent.
Email message
Recipient, subject and contents of the e-mail can be configured freely. To be able to
send e-mail messages, access to the mail server must be configured and mail must
be activated as a communication channel. All necessary settings can be made un-
der Communication channels „ Mail. In the info area you will find the general access
data of the most common e-mail providers.