Byte Bit
Short
code
Description
4
3
MINCRRNT_2
Value is below minimum current. The bit is set if there is an
underflow in the ”Min. current” when the motor is started. This bit
can be used to display the failure of all 3 phases or to indicate that
no loads are connected to the motor starter. It is automatically reset
if the event no longer exists
4
COMERR_2
Communication error. The bit is set if invalid commands are
generated due to false inputs or synchronisation errors. It is
automatically reset if the event no longer exists
5
ENDSTUFE_2
Indicates the status of the control bit ”Output module ON”
6
Not used, always 0
7
Not used, always 0
5
Reserved
6
ACTUAL_CURRENT_2
Actual current of motor 2, range 0 mA – 5.1 A
in units of 20 mA (250 => 5.0 A)
6.5.1.2 Output
bytes
Byte Bit
Short
code
Description
0
0
A0
Binary output A0
1
A1
Binary output A1
2
Not used, always 0
3
Not used, always 0
4
Not used, always 0
5
Not used, always 0
6
Not used, always 0
7
Not used, always 0
1
0
ENABLE_1
Enable / Delete error, motor 1
1
MOT_EIN_1
Motor 1 ON (direction dependent on phase of supply)
2
Not used, always 0
3
Not used, always 0
4
ENABLE_2
Enable / delete error, motor 2
5
MOT_EIN_2
Motor 2 ON (direction dependent on phase of supply)
6
Not used, always 0
7
ERR_QUITT Acknowledge
error