KLIC-DD3
http://www.zennio.com
Technical Support:
http://support.zennio.com
16
“[AC] Temperature Setpoint (Status)”
: 2-Byte object that provides the
Temperature setpoint status.
Note
:
A X.Y value will be rounded to X.0 if [Y < 5] or to X.5 if
[Y ≥ 5].
Status object will be updated to the last setpoint temperature value received by the A/C
unit after a complete communication cycle and will be sent to KNX bus every time that
its value changes.
Setpoint limits can be configured by parameter:
Setpoint Limits
: allows restricting the range of the temperature setpoint
(from below in the Cooling, Dry and Auto modes and from above in the
Heating and Auto modes), provided that the limits are still within the
predefined limits of the A/C unit. When KLIC-DD3 receives an order to send
the A/C unit a setpoint which is greater (or lower) than the configured limits, it
will actually send the limit value.
Minimum (Cooling / Auto / Dry Mode)
: sets the upper limit.
Maximum (Heating / Auto Mode)
: sets the lower limit.
Figure 9.
AC Gateway. Configuration. Temperature setpoint.
Once these limits are enabled, several objects to modify them at run time will be
available. The values of this objects will be restrict to an interval which is defined by the
absolute limits established by the A/C unit (10ºC to 32ºC).
“[AC] Temperature Setpoint: Lower Limit”
: 2-Byte object that allows
changing the lower limit at run time.
“[AC] Temperature Setpoint: Lower Limit (Status)”
: 2-Byte object with the
lower limit current value.