KLIC-PA
Technical Support:
32
205
1 Byte
O
C T R - -
DPT_HVACContrMode
1 = Heat
3 = Cool
9 = Fan
14 = Dry
[AC] Mode (Status)
1 = Heating; 3 = Cooling; 9 = Fan;
14 = Dry
1 Byte
O
C T R - -
DPT_HVACContrMode
0 = Auto
1 = Heat
3 = Cool
9 = Fan
14 = Dry
[AC] Mode (Status)
0 = Automatic; 1 = Heating; 3 =
Cooling; 9 = Fan; 14 = Dry
206
1 Bit
I
C - - W -
DPT_Heat_Cool
0/1
[AC] Simplified Mode
0 = Cooling; 1 = Heating
207
1 Bit
O
C T R - -
DPT_Heat_Cool
0/1
[AC] Simplified Mode (Status)
0 = Cooling; 1 = Heating
208
1 Bit
I
C - - W -
DPT_Switch
0/1
[AC] On/Off
0 = Off; 1 = On
209
1 Bit
O
C T R - -
DPT_Switch
0/1
[AC] On/Off (Status)
0 = Off; 1 = On
210
1 Bit
O
C T R - -
DPT_Bool
0/1
[AC] Internal Error: Communication
Unable to Set AC Communication
211
1 Bit
O
C T R - -
DPT_Bool
0/1
[AC] Internal Error: Timeout
No Acknowledgement Received from
AC
212
1 Bit
O
C T R - -
DPT_Alarm
0/1
[AC] AC Unit Error: Active Error
AC Unit Error
213
14 Bytes
O
C T R - -
DPT_String_ASCII
[AC] AC Unit Error: Error Code
See AC Unit Manual
214
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
[AC] Speed: Percentage Control
0% = Automatic; [0.4...33.3]% =
S1; [33.8...66.6]% = S2;
[67.1...100]% = S3
215
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[AC] Speed: Percentage Control
(Status)
Automatic = 0%; S1 = 33.3%; S2
= 66.7%; S3 = 100%
216
1 Bit
I
C - - W -
DPT_Switch
0/1
[AC] Speed: Automatic
0 = Automatic Off; 1 = Automatic
On
1 Bit
I
C - - W -
DPT_Switch
0/1
[AC] Speed: Automatic
0 = Automatic On; 1 = Automatic
Off
217
1 Bit
O
C T R - -
DPT_Switch
0/1
[AC] Speed: Automatic (Status)
0 = Automatic Off; 1 = Automatic
On
1 Bit
O
C T R - -
DPT_Switch
0/1
[AC] Speed: Automatic (Status)
0 = Automatic On; 1 = Automatic
Off
218
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
[AC] Flaps: Percentage Control
0% = Swing; [0.4...20]% = P1;
[20.4...40]% = P2; [40.4...60]% =
P3; [60.4...80]% = P4;
[80.4...100]% = P5
219
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[AC] Flaps: Percentage Control
(Status)
Swing= 0%; P1 = 20%; P2 = 40%;
P3 = 60%; P4 = 80%; P5 = 100%
220
1 Bit
I
C - - W -
DPT_Switch
0/1
[AC] Flaps: Swing
0 = Swing Off; 1 = Swing On
1 Bit
I
C - - W -
DPT_Switch
0/1
[AC] Flaps: Swing
0 = Swing On; 1 = Swing Off
221
1 Bit
O
C T R - -
DPT_Switch
0/1
[AC] Flaps: Swing (Status)
0 = Swing Off; 1 = Swing On
1 Bit
O
C T R - -
DPT_Switch
0/1
[AC] Flaps: Swing (Status)
0 = Swing On; 1 = Swing Off
222
1 Bit
I
C - - W -
DPT_Switch
0/1
[AC] Flaps: Standby
0 = Standby Off; 1 = Standby On