GEM80
5. Operation
Issue 002 (07/05)
Fieldbus Technical Manual T2035
Page 8
Table 5-1 P Table Configuration Parameters
Table
Function
Comment
P74
Pointer to configuration data.
e.g. 300 = parameters start at P300
MODULE #1 parameters
Pn
Validity flag
@4801 ( Must be this value )
Pn+1
Device type (HIGH)
Pn+2
Device type (LOW)
Safety Check
Pn+3
Scan Rate
Rate in ms, 0 = free running
Pn+4
Input table letter
In LS byte, MS byte =0.
Pn+5
Input table offset
Pn+6
Input table quantity
Pn+7
Output table letter
In LS byte, MS byte =0.
Pn+8
Output table offset
Pn+9
Output table quantity
Pn+10
Version table letter
In LS byte, MS byte =0.
Pn+11
Version table offset
Pn+12
Version table quantity
Pn+13
Reserved
(Must be 0)
Pn+14
Reserved
(Must be 0)
Pn+15
Reserved
(Must be 0)
MODULE #2 parameters
Pn+16
Validity flag
@4802 ( Must be this value )
Pn+17
Device type (HIGH)
Pn+18
Device type (LOW)
Safety Check
Pn+19
Scan Rate
Rate in ms, 0 = free running
Pn+20
Input table letter
In LS byte, MS byte =0.
Pn+21
Input table offset
Pn+22
Input table quantity
Pn+23
Output table letter
In LS byte, MS byte =0.
Pn+24
Output table offset
Pn+25
Output table quantity
Pn+26
Version table letter
In LS byte, MS byte =0.
Pn+27
Version table offset
Pn+28
Version table quantity
Pn+29
Reserved
(Must be 0)
Pn+30
Reserved
(Must be 0)
Pn+31
Reserved
(Must be 0)