GEM80
6. Maintenance and Fault Finding
Issue 002 (07/05)
Fieldbus Technical Manual T2035
Page 12
6.
Maintenance and Fault Finding
6.1
Fixed F-Table
This section contains general guidance for the maintenance of a controller containing
Fieldbus modules.
Each module is allocated 14 fixed F-Tables, used to report errors and statistical
information.
F-Table
Module 1
F-Table
Module 2
Description
Notes
F372
F386
Error Code
F373
F387
Pointer 1
F374
F388
Pointer 2
F375
F389
Exchange Mode
F376
F390
Exchange Counter (LS word)
F377
F391
Exchange Counter (MS word)
F378
F392
F379
F393
F380
F394
F381
F395
F382
F396
F383
F397
F384
F398
F385
F399
Presence Indication
6.1.1
Error Code
The Error Code field and the associated pointers are used to identify problems with the
configuration data or failure of the associated Fieldbus module. On power-up these
fields are cleared. On recompilation, syntax checking is performed on the configuration
and problems are reported as follows.
Error Code
Value
States
On
Fault/Warning
Condition
Comment
5
2 & 0
Fault
Table
Fault
The parameter indicated by
Pointer 1 is a disallowed table.
OR
The parameters indicated by
Pointers 1 & 2 would cross the
table boundary.
Modify user program.
9
3 & 0
Fault
Parameter
Fault
The parameter indicated by
Pointer 1 is out of range.
Modify user program.
17
4 & 0
Fault
Module
No module of the selected type is