Commissioning
EL6201
133
Version: 2.2
Bit
Value
Description
0 - 3
0 - 15
(default 0)
ID code (B-slave)
4 - 6
-
reserved
7
0
Value is taken into account when comparing set/actual configuration in protected mode
1
Value is ignored when comparing set/actual configuration in protected mode
Index 8pp0 ASI Settings Slave (for 01 ≤ pp ≤ 1F; slave 1 to slave 31)
Index (hex) Name
Meaning
Data type
Flags
Default
8pp0:27
Extended ID Code 1
(B-slave)
Projected extended ID code 1 (nominal configuration)
In protected mode, the extended ID code 1 of the cur-
rently projected AS-i slaves is checked. The projected 4-
bit Extended ID codes 1 of the AS-i slaves are located in
the object 0x8pp0:22 (these objects are read-write and
are saved in the Flash of the AS-i master (i.e. they are
still present after power off/on)): (see following table)
UINT8
RW
0x00 (0
dec
)
Bit
Value
Description
0 - 3
0 - 15
(default 0)
Extended ID Code 1 (B-slave)
4 - 6
-
reserved
7
0
Value is taken into account when comparing set/actual configuration in protected mode
1
Value is ignored when comparing set/actual configuration in protected mode
Index 8pp0 ASI Settings Slave (for 01 ≤ pp ≤ 1F; slave 1 to slave 31)
Index (hex) Name
Meaning
Data type
Flags
Default
8pp0:28
Extended ID Code 2
(B-slave)
Projected extended ID code 2 (nominal configuration)
In protected mode, the extended ID code 2 of the cur-
rently projected AS-i slaves is checked. The projected 4-
bit Extended ID codes 1 of the AS-i slaves are located in
the object 0x8pp0:23 (these objects are read-write and
are saved in the Flash of the AS-i master (i.e. they are
still present after power off/on)): (see following table)
UINT8
RW
0x00 (0
dec
)
Bit
Value
Description
0 - 3
0 - 15
(default 0)
Extended ID Code 2 (B-slave)
4 - 6
-
reserved
7
0
Value is taken into account when comparing set/actual configuration in protected mode
1
Value is ignored when comparing set/actual configuration in protected mode
Index 8pp0 ASI Settings Slave (for 01 ≤ pp ≤ 1F; slave 1 to slave 31)
Index (hex) Name
Meaning
Data type
Flags
Default
8pp0:29
Parameter (B-slave)
Activation parameters for the AS-i slaves
During the activation phase (or during the inclusion
phase - for AS-i slaves that are added later), 4-bit param-
eter data are sent once to each AS-i slave prior to the
first data exchange. These activation parameters can be
specified for each AS-i slave via the objects 0x8pp0:24.
The objects 0x8pp0:24 can be read and written and are
saved in the Flash of the AS-i master, i.e. they are still
present after power off/on of the AS-i master. (see follow-
ing table)
UINT8
RW
0x07 (7
dec
)
Bit
Value
Description
0 - 2
0 - 7
(default 7)
Parameter (B-slave)
3 - 7
-
reserved