13-52 SL Controller Action
Option:
Function:
[16] Select preset
ref 6
Selects preset reference 6. If the active
preset reference is changed, it merges with
other preset reference commands coming
from either the digital inputs, or via a
fieldbus.
[17] Select preset
ref 7
Selects preset reference 7. If the active
preset reference is changed, it merges with
other preset reference commands coming
from either the digital inputs, or via a
fieldbus.
[18] Select ramp 1 Selects ramp 1.
[19] Select ramp 2 Selects ramp 2.
[22] Run
Issues a start command to the frequency
converter.
[23] Run reverse
Issues a start reverse command to the
frequency converter.
[24] Stop
Issues a stop command to the frequency
converter.
[25] Qstop
Issues a quick stop command to the
frequency converter.
[26] DC Brake
Issues a DC-brake command to the
frequency converter.
[27] Coast
The frequency converter coasts immediately.
All stop commands including the coast
command stop the SLC.
[28] Freeze output Freezes the output of the frequency
converter.
[29] Start timer 0
See
parameter 13-20 SL Controller Timer
for
further description.
[30] Start timer 1
See
parameter 13-20 SL Controller Timer
for
further description.
[31] Start timer 2
See
parameter 13-20 SL Controller Timer
for
further description.
[32] Set digital
out A low
Any output with SL output A is low.
[33] Set digital
out B low
Any output with SL output B is low.
[34] Set digital
out C low
Any output with SL output C is low.
[35] Set digital
out D low
Any output with SL output D is low.
[38] Set digital
out A high
Any output with SL output A is high.
[39] Set digital
out B high
Any output with SL output B is high.
[40] Set digital
out C high
Any output with SL output C is high.
[41] Set digital
out D high
Any output with SL output D is high.
13-52 SL Controller Action
Option:
Function:
[60] Reset
Counter A
Resets Counter A to zero.
[61] Reset
Counter B
Resets Counter B to zero.
[70] Start Timer 3 See
parameter 13-20 SL Controller Timer
for
further description.
[71] Start Timer 4 See
parameter 13-20 SL Controller Timer
for
further description.
[72] Start Timer 5 See
parameter 13-20 SL Controller Timer
for
further description.
[73] Start Timer 6 See
parameter 13-20 SL Controller Timer
for
further description.
[74] Start Timer 7 See
parameter 13-20 SL Controller Timer
for
further description.
Parameter Descriptions
Programming Guide
MG06C602
Danfoss A/S © 7/2015 All rights reserved.
93
4
4