13-52 SL Controller Action
Array [20]
Select the action corresponding to the SLC event. Actions are
executed when the corresponding event (defined in
parameter 13-51 SL Controller Event
) is evaluated as true. The
following actions are available for selection:
Option:
Function:
reference commands coming from
either the digital inputs or via a
fieldbus.
[18]
Select ramp 1
Selects ramp 1.
[19]
Select ramp 2
Selects ramp 2.
[22]
Run
Issues a start command to the
frequency converter.
[23]
Run reverse
Issues a start reverse command to
the frequency converter.
[24]
Stop
Issues a stop command to the
frequency converter.
[25]
Qstop
Issues a quick stop command to
the frequency converter.
[26]
DC Brake
Issues a DC stop command to the
frequency converter.
[27]
Coast
The frequency converter coasts
immediately. All stop commands
including the coast command stop
the SLC.
[28]
Freeze output
Freezes the output frequency of the
frequency converter.
[29]
Start timer 0
Starts timer 0, see
parameter 13-20 SL Controller Timer
for further description.
[30]
Start timer 1
Starts timer 1, see
parameter 13-20 SL Controller Timer
for further description.
[31]
Start timer 2
Starts timer 2, see
parameter 13-20 SL Controller Timer
for further description.
[32]
Set digital out
A low
Any output with
digital output 1
selected is low (off).
[33]
Set digital out
B low
Any output with
digital output 2
selected is low (off).
[34]
Set digital out
C low
Any output with
digital output 3
selected is low (off).
[35]
Set digital out
D low
Any output with
digital output 4
selected is low (off).
[38]
Set digital out
A high
Any output with
digital output 1
selected is high (closed).
[39]
Set digital out
B high
Any output with
digital output 2
selected is high (closed).
13-52 SL Controller Action
Array [20]
Select the action corresponding to the SLC event. Actions are
executed when the corresponding event (defined in
parameter 13-51 SL Controller Event
) is evaluated as true. The
following actions are available for selection:
Option:
Function:
[40]
Set digital out
C high
Any output with
digital output 3
selected is high (closed).
[41]
Set digital out
D high
Any output with
digital output 4
selected is high (closed).
[60]
Reset Counter
A
Resets counter A to zero.
[61]
Reset Counter
B
Resets counter B to zero.
[70]
Start Timer 3
Starts timer 3, see
parameter 13-20 SL Controller Timer
for further description.
[71]
Start Timer 4
Starts timer 4, see
parameter 13-20 SL Controller Timer
for further description.
[72]
Start Timer 5
Starts timer 5, see
parameter 13-20 SL Controller Timer
for further description.
[73]
Start Timer 6
Starts timer 6, see
parameter 13-20 SL Controller Timer
for further description.
[74]
Start Timer 7
Starts timer 7, see
parameter 13-20 SL Controller Timer
for further description.
[100]
ResetAlarm
Parameters
Programming Guide
MG18P202