P09 Accel.t. 6/11
P
P09
R
0÷6500s
D
10s
Tac3=***s
F
Time interval of acceleration ramp 3 from 0 to Spdmax.
P10 Decel.t. 7/11
P
P10
R
0÷6500s
D
10s
Tdc3=***s
F
Time interval of deceleration ramp 3 from Spdmax to 0.
P11 Accel.t. 8/11
P
P11
R
0÷6500s
D
10s
Tac4=***s
F
Time interval of acceleration ramp 4 from 0 to Spdmax.
P12 Decel.t. 9/11
P
P12
R
0÷6500s
D
10s
Tdc4=***s
F
Time interval of deceleration ramp 4 from Spdmax to 0.
P13 Ramp 10/11
P
P13
R
0÷750rpm
D
2rpm
th.=*.*rpm
F
Determines the time interval of the acceleration and deceleration ramp when ramp
increase is used (P14).
Example : The active ramp is increased by the value set in P14 when going from 0 to
1500 rpm and if P13=30 rpm from 0 to 30 rpm and from 1470 to 1500 rpm both
when accelerating and decelerating.
P14 Ramp 11/11
P
P14
R
1, 2, 4, 8, 16, 32
D
4
Ext =***
F
Multiplicative factor of the active ramp in the time interval defined by parameter P13.
NOTE
The active ramp depends on the condition of inputs MDI4 and MDI5 whether they
are programmed to alter ramp times (see “Operation method” submenu,
parameters C20 and C21).