AUTOMATIC DOORS FOR LIFTS
8
VF5
PROGRAMMING EXAMPLES
•
MASTER: 1 INPUT
- Configuration
1. ON: 1 Input.
2. Depends on type of door.
3. Depends on type of door.
4. ON: Master.
- Inputs
1.
8
Close.
Closes the doors with voltage between terminals 8 &
10. Open the doors when the voltage between
terminals 8 & 10 is removed.
2.
17...20
Photocell.
Doors will reopen if the photocell beam is broken.
3.
21-23
Reopening. Doors will not close if this signal is active.
4.
Obstacle.
Door will re-open if an obstacle is detected by the
motor ceasing to rotate.
5.
25-23
Slow Closing. Closes regardless of the state of the photocell.
- Priorities
1.
21-23
Reopening.
2.
Obstacle.
3.
25-23
Slow Closing
4.
17...20
Photocell.
5.
8
Close.
•
SLAVE: 2 INPUTS
- Configuration
1. ON: 2 Inputs.
2. Depends on type of door.
3. Depends on type of door.
4. ON: Slave.
- Inputs
1.
8
Close.
Closes the doors with voltage between terminals 8 &10.
2.
12
Open.
Open the doors with voltage between terminals 12 &
10.
3.
17...20
Photocell.
Does not re-open the doors when activated but provides
signal to main controller via the Photocell
relay.
4.
21-23
Reopening. Doors will not close if this signal is active.
5.
Obstacle.
Door will not re-open if an obstacle is detected by the
motor ceasing to rotate.
6.
25-23
Slow Closing. Closes regardless of the state of the photocell.
- Priorities
1.
12
Open.
2.
21-23
Reopening
3.
25-23
Slow Closing.
4.
8
Close.