73
31-00083—02
nviSetPoint
temp_p
F
Input network variable used to determine the temperature control point
(center setpoint) of the node. If nviSetPoint is valid, then it is used to
determine the control point of the node. If nviSetPoint is invalid, then other
means are used to determine the control point
40
≤
range
≤
100 F
where:
ZEB_OCC = OccCool - OccHeat
ZEB_STDBY = StandbyCool - StandbyHeat
Setpoint Override Priority
Note: This input is intended for a network connected wall module.
nviSetPointOvr
temp_p
F
Input network variable used to temporarily override the temperature
control center setpoint. Please refer to nviSetPoint for details.
40
≤
range
≤
100 F
Setpoint Override Priority
Note: This input is dedicated to a workstation or network connected tool
and should not be bound to a network wall module.
nviSetPtOffset
temp_diff_p
Delta F
This network input is used to temporarily shift the effective heating and
cooling setpoint. The value is added to the effective setpoint. The shift is
effective setpoint for Occupied, Bypass and Standby modes.
-10 < range < +10
∆
F
Setpoint Override Priority
Table 21. Network Variable - Inputs (Continued)
Nv/field
Net Data Type
SNVT
AP Internal
Units
Description
New “Temporary” Variables
OccCool = nviSe ZEB_OCC / 2
OccHeat = nviSetPoint - ZEB_OCC / 2
StandbyCool = nviSe ZEB_STDBY / 2
StanbyHeat = nviSetPoint - ZEB_STDBY / 2
Priority
Setpoint Input
1
nviSetPointOvr
2
nviSetPoint
3
nviSetPtOffset
4
Wall Module center setpoint
Priority
Setpoint Input
1
nviSetPointOvr
2
nviSetPoint
3
nviSetPtOffset
4
Wall Module center setpoint
Priority
Setpoint Input
1
nviSetPointOvr
2
nviSetPoint
3
nviSetPtOffset
4
Wall Module center setpoint