4.6.5
CO2_IN_ALARM_FLASHING_LCD (Register 40205, bit 5)
Bit 5 of register 40205 switch on function LCD background illumination flashing when
CO2 alarm occur. When bit 5 is
“true”
CO2 Alarm is indicated by LCD display flashing.
Read more about CO2 Alarm in CO2 sensor. By default bit is
“false”
(function
deactivated).
4.6.6
CO2_IN_ALARM_BUZZER (Register 40205, bit 6)
Bit 6 of register 40205 switch on buzzer when CO2 alarm occur. When bit 6 is
“true”
CO2
Alarm is indicated by the beeper which emits sound with 1 Hz frequency. Read more
about CO2 Alarm in CO2 sensor. By default bit is
“false”
(function deactivated).
4.6.7
CO2_IN_ALARM_SHOW_HIGH (Register 40205, bit 7)
Bit
7 of register 40205 switch on “HIGH” label on display when CO2 alarm occur.
When bit
7 is
“true”
and CO2 Alarm is active LCD display shows CO2 sensor actual value on 8-
segment displays block and blinking text “HIGH” on 14
-segment displays block. By default
bit is
“false”
(function deactivated).
4.6.8
SUBMENU_ICON_DISPLAY_OFF (Register 40205, bit 10)
Bit 10 of register 40205 switch off submenu icon display. When bit 10 is
“true”
all
submenu icons are hidden, even in the case when one or more submenus contain active
points. The user can enter active submenu (with at least one active point) and proceed
normal operation , but its icon is invisible in the Mail Menu display view.
4.6.9
PANEL_OFF (Register 40205, bit 11)
Bit 11 of register 40205 switch off panel. When bit 11 is
“true”
the Room Panel is inactive.
It means that it is impossible to control The Room Panel locally (access to submenus and
parameters configuration is blocked
–
Key Pad is deactivated). LCD display and
background illumination are also OFF. The main menu is not displayed. The Room Panel
works as temperature sensor (or multisensor if CO2 sensor or humidity sensor are built-
in). When the bit 12 is
“false”
the Room Panel works in normal mode (functions for local
control are active). By default bit is
“false”
(Panel ON).
4.6.10
KEY_PAD_OFF (Register 40205, bit 12)
Bit 12 of register 40205 switch off panel key pad. When bit 12 is active Key Pad function
is deactivated. Single pushing any button emits beeper sound (if beeper is activated) and
activates the Active Mode (set background illumination level) but submenu access is
blocked (it is impossible to enter any Menu and to change any parameters and settings).