iSMA-B-LP Room Panel/Modbus
version 1.3
www.gc5.pl
Page 74 / 121
Modbus
Address
Dec
Address
Hex
Address
Register Name
Access
Description
FALSETEXT (32
–
bits)
Write
Memory
40429
428
0x1AC
MAIN_MENU_BOOLEAN8
PRIORITY
Read &
Write
Memory
Priority of the parameter for sequence of display in
Main Menu
40440
429
0x1AD
MAIN_MENU_BOOLEAN8
CONFIGURATION
Read &
Write
Memory
Bit
Name
0
1
0
Active
Not active(def)
Active
12.1.3
Temperature Submenu
Modbus
Address
Dec
Address
Hex
Address
Register Name
Access
Description
40059
58
0x3A
TEMPERATURE_NUMERIC1
PRESENT_VALUE
Read &
Write
Memory
Present value of the parameter
40501
500
0x13F
TEMPERATURE_MENU
ACTIVE_POINTS
Read &
Write
Memory
Number of active parameters in submenu
40504
503
0x1F7
TEMPERATURE_NUMERIC1
NAME (32
–
bits)
Read &
Write
Memory
Displaying user-defined parameter name.
40506
505
0x1F9
TEMPERATURE_NUMERIC1
STEP
Read &
Write
Memory
STEP during parameter value changing.
The default value is 0
40507
506
0x1FA
TEMPERATURE_NUMERIC1
LOW_LIMIT
Read &
Write
Memory
Minimal value of the parameter.
The default value is 0
40508
507
0x1FB
TEMPERATURE_NUMERIC1
HIGH_LIMIT
Read &
Write
Memory
Maximal value of the parameter.
The default value is 0
40509
508
0x1FC
TEMPERATURE_NUMERIC1
PRIORITY
Read &
Write
Memory
Priority of the parameter for sequence of display in
Submenu