KNX/EIB
Switch Actuator with Secure
52
5.2.3. Preset function object of “Switch actuator"
Fig. 5.2.3 Preset function communication object for every output of “Switch Actuator”
No.
Function
Object name
Data type
Flags
DPT
10
Recall preset
Output A-{{...}} 1bit
C,W
1.022 scene
This object is used to call the preset value;telegram “0” with “0” and telegram “1” with “1”
11
Store preset
Output A-{{...}} 1bit
C,W
1.022 scene
It can be used to save the current switch status as the new preset value; save the new telegram
“0” with “0” and telegram “1” with “1”.
Table 5.2.3 Preset communication objects
5.2.4. Logic function object of “Switch actuator”
Fig. 5.2.4 Logic function communication object for every output of “Switch Actuator”
No.
Function
Object name
Data type
Flags
DPT
12
Input 1 of logic
Output A-{{...}}
1bit
C,W
1.002 boolean
This object will be enabled when selecting “Enable” in the parameter “The input 1 of logic is”.
13
Input 2 of logic
Output A-{{...}}
1bit
C,W
1.002 boolean
This object will be enabled when selecting “Enable” in the parameter “The input 2 of logic is”.
Table 5.2.4 Logic function communication objects