45
90
Setpoint
HVAC
2 byte
C,R,W,T
This communication object is used to modify the temperature setpoint or send out the setpoint, read out the
setpoint on the bus according to the parameter setting. Temperature range: 10…40
℃
91
Heating control value
HVAC
1bit/byte
C,R,T
The communication object is used to send out the control value for heating function on the bus to control
temperature controller on/off.
Telegram value (2-point 1bit): on/off
Telegram value (2-point 1byte): 0%/100%
Telegram value (PI continuous): 0…100%
Telegram value (PI PWM 1bit): on/off
Telegram value (Fan coil): 0...100%
92
Switchover heating/cooling
HVAC
1bit
C,R,T
The communication object will be visible with ―heating and cooling‖ in the parameter ―control function‖,
which is used to send out a telegram to switch between the heating function and the cooling function.
Telegram value:
1——heating function
0——cooling function
93/98
Fan level, heating/cooling
HVAC
1byte
C,R,T
The communication object can only be used with ―fan coil‖ in the parameter ―control type heating/cooling‖,
which is used to send out a telegram with control fan speed, the telegram value is set via parameter.
Telegram value: 0…100% (0…255)
94
Comfort operating mode
HVAC
1bit
C,R,W,T
The communication object will be visible with ―1bit‖ in the parameter ―object for operating mode change‖, if
a telegram ―1‖ is sent out at this communication object, the operating mode is switched to the comfort mode for
the temperature controller.
Telegram value:
1——the comfort mode
0——the comfort mode off
94
RTC operating mode
HVAC
1byte
C,R,W,T
The communication object will be visible with ―1byte‖ in the parameter ―object for operating mode change‖,
which is used to send out different telegram values, different values mean different operating mode:
1—comfort mode
2—standby mode
3—night mode
4—frost/heating protection mode
95
Night operating mode
HVAC
1bit
C,R,W,T
The communication object will be visible with ―1bit‖ in the parameter ―object for operating mode change‖; if
a telegram ―1‖ is sent out at this communication object, the operating mode is switched to the night mode for the
temperature controller.
Telegram value:
1——the night mode
0——the night mode off