[ENG] 14.5. [DKSF 48.4 IU] Temperature Sensor Management
An interface of URL-encoded commands in a device can be used to integrate with web applications without using an SNMP protocol. Through the
interface of URL-encoded commands, it is possible to control temperature sensors.
Status Request
where:
N is a number of a temperature sensor, specified after .
–
?t
Returned Values
An error in a request (incorrect format, wrong number of a sensor):
Successful completion of a command:
where:
The first argument is always 'ok' ('error' if a request is faulty).
The second argument is a current temperature.
The third argument is status of a sensor
0 a sensor is not connected or failed
–
1 a temperature is below normal
–
2 a temperature is normal
–
3 a temperature is above normal
–
http://192.168.0.100
/thermo.cgi?tN
thermo_result('error')
thermo_result('ok', 36, 2);