Copyright © NetPing east Co., Ltd E-mail:
Phone:+886-2-23121582
support@netpingdevice.com
.1.3.6.1.4.1.25728.8200.1.1.1.n
npSmokeSensorN.n
Integer
READ
An index of a 1-wire smoke sensor, where n – is a number of a smoke sensor, a
number from 1 to 4 inclusive
.1.3.6.1.4.1.25728.8200.1.1.2.n
npSmokeStatus.n
Integer
READ
A status of a 1-wire smoke sensor n, where n – is a number of a smoke sensor, a
:
number from 1 to 4 inclusive
0 – Norm
1 – Alert
4 – Disabled
5 – Failure
.1.3.6.1.4.1.25728.8200.1.1.3.n
npSmokePower.n
Integer
READ/WRITE Powering of a 1-wire smoke sensor, where n – is a smoke sensor number, a number
:
from 1 to 4 inclusive
0 – Off
1 – On
.1.3.6.1.4.1.25728.8200.1.1.4.n
npSmokeReset.n
Integer
READ/WRITE Reset of a power supply of a 1-wire smoke sensor. Write a number «1» to disable a
sensor for 10 seconds, where n – is a smoke sensor number, a number from 1 to 4
inclusive
.1.3.6.1.4.1.25728.8200.1.1.6.n
npSmokeMemo.n
DisplayString
READ
A memo of a 1-wire smoke sensor, where n – is a smoke sensor number, a number
from 1 to 4 inclusive
.1.3.6.1.4.1.25728.8400.2.2.0
npRelHumSensorValueH
Integer
READ
A relative humidity value, %.
.1.3.6.1.4.1.25728.8400.2.3.0
npRelHumSensorStatus
Integer
READ
A humidity sensor status:
0 – Normal
1 – Error or a sensor is not connected
.1.3.6.1.4.1.25728.8400.2.4.0
npRelHumSensorValueT
Integer
READ
A temperature sensor,°C
.1.3.6.1.4.1.25728.8400.2.5.0
npRelHumSensorStatusH
Integer
READ
A humidity sensor status:
0 – A sensor is faulty
1 – Readings of a sensor are below a normal level
2 – Readings of a sensor are normal
3 – Readings of a sensor are above a normal safe range
.1.3.6.1.4.1.25728.8400.2.7.0
npRelHumSafeRangeHigh
Integer
READ
An upper limit of a range of normal values for a humidity sensor
.1.3.6.1.4.1.25728.8400.2.8.0
npRelHumSafeRangeLow
Integer
READ
A lower limit of a range of normal values for a humidity sensor
.1.3.6.1.4.1.25728.8400.2.9.0
npRelHumSensorValueT100
Integer
READ
Readings of a temperature sensor, multiplied by 100. It is used to read readings of a
sensor with decimals and hundredths of a degree Celsius. Divide this value by 100, to
get a current temperature
.1.3.6.1.4.1.25728.8800.1.1.1.n
npThermoSensorN.n
Integer
READ
Temperature sensor identifier, a number from 1 to 8 inclusive
.1.3.6.1.4.1.25728.8800.1.1.2.n
npThermoValue.n
Integer
READ
A current temperature on a temperature sensor, deg. C
where: n – is a number of a temperature sensor, a number from 1 to 8 inclusive
.1.3.6.1.4.1.25728.8800.1.1.3.n
npThermoStatus.n
Integer
READ
A status of a temperature sensor:
0 – Failed or is not connected
1 – Below normal
2 – Normal
3 – Above normal
where: n – is a number of a temperature sensor, a number from 1 to 8 inclusive.
.1.3.6.1.4.1.25728.8800.1.1.4.n
npThermoLow.n
Integer
READ/WRITE A lower threshold of a temperature range of a sensor
where: n – is a number of a temperature sensor, a number from 1 to 8 inclusive.
.1.3.6.1.4.1.25728.8800.1.1.5.n
npThermoHigh.n
Integer
READ/WRITE An upper threshold of a temperature range of a sensor
where: n – is a number of a temperature sensor, a number from 1 to 8 inclusive.
.1.3.6.1.4.1.25728.8800.1.1.6.n
npThermoMemo.n
DisplayString
READ
A memo for a temperature sensor
where: n – is a number of a temperature sensor, a number from 1 to 8 inclusive.
.1.3.6.1.4.1.25728.8900.1.1.1.n
npIoLineN.n
Integer
READ
An identifier of an IO line, n – is a number of a line, a number from 1 to 4 inclusive
.1.3.6.1.4.1.25728.8900.1.1.2.n
npIoLevelIn.n
Integer
READ
A current status of a line
where: n – is a number of a line, a number from 1 to 4 inclusive
.1.3.6.1.4.1.25728.8900.1.1.3.n
npIoLevelOut.n
Integer
READ/WRITE A status of a line in an «output» mode.