127
Numeral Setting
Section 5-4
Data is written to the content upgrade memory table entry as three digits of
BCD (binary coded decimal) data.
When the numeral setting strobe flag bit has been notified to the PLC it
returns to the OFF (0) status.
For details on the method for storing a number in the word allocated for the
numeral memory table entry, see “Allocation Words and Display of the Mem-
ory Table Entries” (page 4).
• Restrictions on allocating words
The PT status notify area can be allocated to the PLC memory areas listed
in the following table.
Words Allocated of the PT
Status Notify Area
Words can be allocated for the PT status notify area (PT
®
host) in the follow-
ing host (PLC) areas.
*1 LR 00000 to LR 00199 are converted to CIO 01000 to CIO 01199.
*2 The EM Area is supported only by the C200HX/HG/HE (-Z)E PLCs.
The range of each memory area differs according to
Appendix H Special
Characters
(page 163) for more details.
Procedure
1.
Use the support tool to allocate the PT status notify area (PT
®
PLC) to the
PLC memory.
2.
Using the support tool, create a numeral setting screen and allocate the
numeral memory table entry to the PLC memory.
3.
Create a PLC program for reading the “content upgrade memory table en-
try” in the PT status notify area when the numeral setting strobe flag in the
PT status notify area comes ON (1).
4.
Read the allocated word for the numeral memory table entry number read
in step 3.
Symbol
C-series PLCs
Allocation
CV-series PLCs
Allocation
CS/CJ-series PLCs
Allocation
None
IR Area
OK
CIO Area
OK
CIO Area
OK
H
HR Area
OK
---
---
HR Area
Not for Host
Link
A
AR Area
OK
Auxiliary Area
No
AR Area
OK
L
LR Area
OK
---
---
LR Area
*1
Not for Host
Link
T
TC Area,
Timer PVs
No
Timer Area,
Timer PVs
No
TC Area,
Timer PVs
No
TU
---
---
---
---
TC Area,
Timer Completion Flags
No
C
TC Area,
Counter PVs
No
Counter Area,
Counter PVs
No
TC Area,
Counter PVs
No
CU
---
---
---
---
TC Area,
Counter Completion Flags
No
W
---
---
---
---
WR Area
Not for Host
Link
TK
---
---
---
---
Task Flags
No
D
DM Area
OK
DM Area
OK
DM Area
OK
E
EM Area
*2
,
current bank
OK
EM Area,
current bank
Not for Host
Link
EM Area,
current bank
Not for Host
Link
E0_ to
EC_
---
---
---
---
EM Area,
EM banks 0 to C
Not for Host
Link
Summary of Contents for NT11 - 01-2004
Page 1: ...USER S MANUAL Cat No V084 E1 01 NT11 Programmable Terminal ...
Page 2: ...NT11 Programmable Terminal User s Manual Produced January 2004 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv Safety Precautions 3 ...
Page 27: ...14 Before Operating Section 1 6 ...
Page 71: ...58 Connecting a Printer Section 2 8 ...
Page 119: ...106 Daily Report Display History Printing Function Section 4 10 ...
Page 157: ...144 Inspection and Cleaning Section 6 3 ...
Page 162: ...149 Appendix B Dimensions Body NT11 SF121 B EV1 38 2 7 5 218 203 113 98 ...
Page 163: ...150 Dimensions Appendix B ...
Page 165: ...152 Transporting and Storing the NT11 Appendix C ...
Page 183: ...170 Revision History ...
Page 186: ...NT11 Programmable Terminal Cat No V084 E1 01 USER S MANUAL ...