IG-267-EN versión 01; 07/04/2017
105
General Instructions
ekor
.rpa
Communications
Clock (0 x 03XX)
Address
Field
Description
Size
Read/write
0 x 0300
YEAR
Year (from 2000 to 2059)
16 bits
Read/write
0 x 0301
MONTH
DAY
Month (from 1 to 12)
DAY (FROM 1st to 31st)
16 bits
Read/write
0 x 0302
TIME
MIN
Time (FROM 0 to 23)
MINUTE (from 0 to 59)
16 bits
Read/write
0 x 0303
00
SEC
0
SECOND (from 0 to 59)
16 bits
Read/write
Table 12.7.
Clock
Password (0 x 05XX)
Address
Field
Description
Size
Read/write
0 x 0500
User Key.
Key to access settings with user privileges
(From 0 to 9999)
16 bits
Write-only
Table 12.8.
Password
Commands and outputs (0 x 06XX)
Address
Field
Description
Size
Read/write
0 x 0600
cmb0-cmb15
Write: From cmb0 (LSB) to cmb15 (MSB)
Read: From SAL1 (LSB) to SAL7 and from cmb7 to cmb15 (MSB)
16 bits
Read/write
0 x 0601
cmb16-cmb31
Read and write: From cmb16 (LSB) to cmb31 (MSB)
16 bits
Read/write
0 x 0602
cmb32-cmb47
Read and write: From cmb32 (LSB) to cmb47 (MSB)
16 bits
Read/write
0 x 0603
cmb48-cmb63
Read and write: From cmb48 (LSB) to cmb63 (MSB)
16 bits
Read/write
Table 12.9.
Command and outputs
Meterings and statuses (0 x 07XX)
Address
Field
Description
Size
Read/write
0 x 0700
VA
A Phase voltage (Volts)
32 bits
Read
0 x 0702
VB
B Phase voltage (Volts)
32 bits
Read
0 x 0704
VC
C Phase voltage (Volts)
32 bits
Read
0 x 0706
VN
Neutral voltage (Volts)
32 bits
Read
0 x 0708
IA
A phase current (Hundredths of an ampere)
32 bits
Read
0 x 070A
IB
B phase current (Hundredths of an ampere)
32 bits
Read
0 x 070C
IC
C phase current (Hundredths of an ampere)
32 bits
Read
0 x 070E
INS
Sensitive neutral current (Hundredths of an ampere)
32 bits
Read
0 x 0710
emb0-emb15
MODBUS statuses of the 0 (LSB)–15 (MSB)
16 bits
Read
0 x 0711
emb16-emb31
MODBUS statuses of the 16 (LSB)–31 (MSB)
16 bits
Read
0 x 0712
emb32-emb47
MODBUS statuses of the 32 (LSB)–47 (MSB)
16 bits
Read
0 x 0713
emb48-emb63
MODBUS statuses of the 48 (LSB)–63 (MSB)
16 bits
Read
0 x 0714
emb64-emb79
MODBUS statuses of the 64 (LSB)–79 (MSB)
16 bits
Read
0 x 0715
emb80-emb95
MODBUS statuses of the 80 (LSB)–95 (MSB)
16 bits
Read
0 x 0716
emb96-emb111
MODBUS statuses of the 96 (LSB)–111 (MSB)
16 bits
Read
0 x 0717
emb112-emb127
MODBUS statuses of the 112 (LSB)–127 (MSB)
16 bits
Read
0 x 0718
PA
Active power of phase A (Watts)
32 bits
Read
0 x 071A
PB
Active power of phase B (Watts)
32 bits
Read
0 x 071C
PC
Active power of phase C (Watts)
32 bits
Read
0 x 071E
PT
Total active power (Watts)
32 bits
Read
0 x 0720
QA
Reactive power of phase A (VAr)
32 bits
Read
0 x 0722
QB
Reactive power of phase B (VAr)
32 bits
Read
0 x 0724
QC
Reactive power of phase C (VAr)
32 bits
Read
0 x 0726
QT
Total reactive power (VAr)
32 bits
Read
0 x 0730
Set at 0 x FF
Set at 0 x FF
16 bits
Read
0 x 0731
ANG(VA/VA)
VA/VA angle [always 0]
16 bits
Read
0 x 0732
ANG(VB/VA)
VB/VA angle [from 0 (0.0°) to 3599 (359.9°)]
16 bits
Read
Continued on next page
Summary of Contents for ekor.rpa Series