Function description
Operating Manual PSSu K F EI
1003303-EN-03
| 31
I-data type: FS_I_EI_PARA
I/O-data name
I/O data element
Meaning
Parameters
Handshake: SAFEBOOL
Module has adopted new parameter value
Parameters
ParameterError: SAFE-
BOOL
TRUE: An incorrect parameter has been trans-
ferred
FALSE: No fault
O-data type: ST_O_DO
I/O-data name
I/O data element
Meaning
O0
Data: BOOL
TRUE: Switch on output 0
FALSE: Switch off output 0
O-data type: FS_O_DO:
I/O-data name
I/O data element
Meaning
O1
Data: SAFEBOOL
TRUE: Switch on output 1
FALSE: Switch off output 1
O2
Data: SAFEBOOL
TRUE: Switch on output 2
FALSE: Switch off output 2
SSM0_DeactivateSS1M
Data: SAFEBOOL
TRUE: Deactivate monitoring function SSM0 for
the outputs.
FALSE: Activate monitoring function SSM0 for
the outputs.
SSM1_DeactivateSS1M
Data: SAFEBOOL
TRUE: Deactivate monitoring function SSM1 for
the outputs.
FALSE: Activate monitoring function SSM1 for
the outputs.
SSRM_DeactivateSS1M
Data: SAFEBOOL
TRUE: Deactivate monitoring function SSRM for
the outputs.
FALSE: Activate monitoring function SSRM for
the outputs.
SOSM_DeactivateSS1M
Data: SAFEBOOL
TRUE: Deactivate monitoring function SOSM for
the outputs.
FALSE: Activate monitoring function SOSM for
the outputs.
SDIM_PosDeactivateSS1M
Data: SAFEBOOL
TRUE: Deactivate monitoring function SDIM-Pos
for the positive direction for the outputs.
FALSE: Activate monitoring function SDIM-Pos
for the positive direction for the outputs.
SDIM_NegDeactivateSS1M
Data: SAFEBOOL
TRUE: Deactivate monitoring function SDIM-Neg
for the negative direction for the outputs.
FALSE: Activate monitoring function SDIM-Neg
for the negative direction for the outputs.